background image

Instructions

2 | AN403622134116en-000102 - 8510312P01AA

 © Danfoss | Climate Solutions | 2022.07

These Danfoss scroll compressor motors are protected by an external 
module protecting against phase loss/reversal, over heating and high 
current draw. 

DSG240 to DSG380

MPM

S

CCH

CC

SS

LPS

UNIT
CONTROLLER

KM

DGT

CB

4 - Electrical connections details

DSG480

Legend:

Fuses .........................................................................................F1
Compressor contactor ........................................................ KM
High pressure safety switch................................................ HP
Discharge gas thermistor  
(embedded in compressors) ............................................ DGT

Crankcase heater ............................................................... CCH
Compressor motor .................................................................M
Motor Protection Module ...............................................MPM
Thermistor chain...................................................................... S

Safety pressure switch ........................................................LPS
Thermal magnetic motor circuit breaker  ....................... CB

CCH

CONTROL
CIRCUIT

LPS

UNIT
CONTROLLER

SEPARATE
SUPPLY

KM

DGT

MPM

S

CB

These Danfoss scroll compressor motors are protected by an external 
module protecting against phase loss/reversal, over heating and high 
current draw. 

Summary of Contents for DSG Series

Page 1: ...t D Supply voltage Starting current Maximum operating current E Housing service pressure F Factory charged lubricant 1 Introduction These instructions pertain to the Danfoss scroll compressors DSG scroll com pressors used for air conditioning systems They provide necessary informa tion regarding safety and proper usage of this product DSG Large Operating map 3 Operating map 2 Nameplate M A D E I N...

Page 2: ...ions details DSG480 Legend Fuses F1 Compressor contactor KM High pressure safety switch HP Discharge gas thermistor embedded in compressors DGT Crankcase heater CCH Compressor motor M Motor Protection Module MPM Thermistor chain S Safety pressure switch LPS Thermal magnetic motor circuit breaker CB CCH CONTROL CIRCUIT LPS UNIT CONTROLLER SEPARATE SUPPLY KM DGT MPM S CB These Danfoss scroll compres...

Page 3: ...the 5 mm earth terminal screw The maximum torque is 4Nm 11 Filling the system Keep the compressor switched off Fill the refrigerant in liquid phase into the condenser or liquid receiver The charge must be as close as possible to the nominal system charge to avoid low pressure operation and excessive superheat Never let the pressure on LP side exceed the pressure on HP side with more than 5 bar Suc...

Page 4: ...ding this product The product warranty may be void in following cases Absence of nameplate External modifications in particular drilling welding broken feet and shock marks Compressor opened or returned unsealed Rust water or leak detection dye inside the compressor Use of a refrigerant or lubricant not approved by Danfoss Any deviation from recommended instructions pertaining to installation appl...