background image

Instructions

4 | AN309640488445en-000201 - 8510290P02B

 © Danfoss | DCS (CC) | 2020.10

5 – Handling and storage

 •  

Handle the compressor with care. Use the 
dedicated handles in the packaging. Use the 
compressor lifting lug and use appropriate and 
safe lifting equipment.

 •  

Store and transport the compressor in an 
upright position.

 •  Store the compressor between Ts min and Ts 

max values for LP side indicated on compressor 
nameplate. 

 

• 

 

Don’t expose the compressor and the 
packaging to rain or corrosive atmosphere.

6 – Safety measures before assembly

 Never use the compressor in a flammable 

atmosphere.
 •  Check before assembly that the compressor 

does not show any obvious signs of 
deterioration that could have occurred during 
inappropriate transportation, handling or 
storage.

  •   The compressor ambient temperature may not 

exceed Ts max value for LP side indicated on 
compressor nameplate during off-cycle.

 •  

Mount the compressor on a horizontal flat 
surface with less than 3° slope.

 •  Verify that the power supply corresponds to 

the compressor motor characteristics (see 

 

nameplate).

 •  Use clean and dehydrated refrigeration-grade 

copper tubes and silver alloy brazing material.

  •   Use clean and dehydrated system components.
  •   The piping connected to the compressor must be 

flexible in 3 dimensions to dampen vibrations.

7 – Assembly

 •   The compressor must be mounted on rails or 

chassis according to Danfoss recommendations 
described in related product guidelines (type 
of spacer, tightening torques).

 •  

Slowly release the nitrogen holding charge 
through the schrader port.

 •  

Remove the gaskets when brazing rotolock 
connectors.

  •   Always use new gaskets for assembly.
  •   Connect the compressor to the system as soon 

as possible to avoid oil contamination from 
ambient moisture.

 •   Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 
cannot be removed.

 •  

Braze with great care using state-of-the-art 
technique and vent piping with nitrogen gas 
flow.

 •  

Connect the required safety and control 
devices. When the schrader port is used for 
this, remove the internal valve.

 •  

Do not exceed the maximum tightening 
torque for rotolock connections:145 Nm.

8 – Leak detection

 Never pressurize the circuit with oxygen or dry 

air. This could cause fire or explosion.
  •   Pressurize the system on HP side first and then 

on LP side. Never let the pressure on LP side 
exceed the pressure on HP side with more than 
5 bar. Such pressure difference could cause 
internal compressor damage.

  •   Do not use dye for leak detection.
 •   Perform a leak detection test on the complete 

system.

 •  The test pressure must not exceed 1.1 x PS 

value for LP side and HP side indicated on 
compressor nameplate.

 •   When a leak is discovered, repair the leak and 

repeat the leak detection.

9 – Vacuum dehydration

 •  

Never use the compressor to evacuate the 
system.

 •   Connect a vacuum pump to both the LP & HP 

sides.

 •   Pull down the system under a vacuum of 500 

µm Hg (0.67 mbar) absolute.

 •   Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 
this may cause internal damage.

10 – Electrical connections

 •   Switch off and isolate the main power supply. 

See overleaf for wiring details.

 •  

All electrical components must be selected 
as per local standards and compressor 
requirements.

 •  Refer to section 4 for electrical connections 

details.

 •  

The Danfoss scroll compressors only works 
correctly in one rotation direction. Line phases 
L1, L2, L3 must absolutely be connected 
to compressor terminals T1, T2, T3 to avoid 
reverse rotation.

 

• 

 

Electrical power is connected to the 
compressor terminals by M5 studs and nuts 
. Use appropriate ring terminals, fasten with 
3Nm torque.

 •  The compressor must be connected to earth 

with the 5 mm earth terminal screw. The 
maximum torque is 4Nm.

11 – Filling the system

  •   Keep the compressor switched off.
 •  

Fill the refrigerant in liquid phase into the 
condenser or liquid receiver. The charge must 
be as close as possible to the nominal system 
charge to avoid low pressure operation and 
excessive superheat. Never let the pressure 
on LP side exceed the pressure on HP side 
with more than 5 bar. Such pressure difference 
could cause internal compressor damage.

 

•  

Keep the refrigerant charge below the 
indicated charge limits if possible. Above this 
limit; protect the compressor against liquid 
flood-back with a pump-down cycle or suction 
line accumulator.

 •  Never leave the filling cylinder connected to 

the circuit.

Compressor models

Refrigerant charge 

limit (kg)

DSF270, DSF325

15

DSF485, DSF530

17

12 – Verification before commissioning

 Use safety devices such as safety pressure 

switch and mechanical relief valve in compliance 
with both generally and locally applicable 
regulations and safety standards. Ensure that 
they are operational and properly set. 

 Check that the settings of high-pressure 

switches and relief valves don’t exceed the 
maximum service pressure of any system 
component.

 •  

A low-pressure switch is recommended to 
avoid vacuum operation. Minimum setting for 
1.7 bar g.

 •  

Verify that all electrical connections are 
properly fastened and in compliance with local 
regulations.

  •   When a crankcase heater is required, it must be 

energized at least 12 hours before initial start-
up and start-up after prolonged shutdown for 
belt type crankcase heaters (6 hours for surface 
sump heaters).

13 – Start-up

 Never operate the compressor without the 

electrical box cover fitted.
  •   Never start the compressor when no refrigerant 

is charged.

  •   All service valves must be in the open position.
  •   Balance the HP/LP pressure.
  •   Energize the compressor. It must start promptly. 

If the compressor does not start, check wiring 
conformity and voltage on terminals.

 •  Eventual reverse rotation can be detected by 

following phenomena; the compressor doesn’t 
build up pressure, it has abnormally high sound 
level and abnormally low power consumption. 
In such case, shut down the compressor 
immediately and connect the phases to 
their proper terminals. DSF compressors are 
protected against reverse rotation by the 
external electronic protection module. They 
will shut off automatically. 

 •  If the internal pressure relief valve is opened 

the compressor sump will be warm and 
the compressor will trip out on the motor 
protector.

14 – Check with running compressor

  •   Check current draw and voltage.
 •  

Check suction superheat to reduce risk of 
slugging.

  •   Observe the oil level in the sight glass for about 

60 minutes to ensure proper oil return to the 
compressor.

  •   Respect the operating limits.
 

•  

 

Check all tubes for abnormal vibration. 
Movements in excess of 1.5 mm require 
corrective measures such as tube brackets.

 •  When needed, additional refrigerant in liquid 

phase may be added in the low-pressure side 
as far as possible from the compressor. The 
compressor must be operating during this 
process.

  •   Do not overcharge the system.
  •   Never release refrigerant to atmosphere.
 •  For reversible systems, ensure that the 4-way 

valve does not reverse when the compressor 
is stopped due to heating or cooling demand 
(stop on thermostat)

 •  Before leaving the installation site, carry out 

a general installation inspection regarding 
cleanliness, noise and leak detection.

 •   Record type and amount of refrigerant charge 

as well as operating conditions as a reference 
for future inspections.

15 – Maintenance

 Internal pressure and surface temperature 

are dangerous and may cause permanent injury.
Maintenance operators and installers require 
appropriate skills and tools. Tubing temperature 
may exceed 100°C and can cause severe burns.

Reviews: