DMS Manual
Setting up
DMS
■
Adjustment/ Settings
DMS adjustments are made using the DIP switch
adjustment panel located on the underside of
the Electronics module.
Section
Switch no.
Description
Value
Factory setting
1
Off
2
Off
3
Off
4
Start/ stop
profile setting
Selection of
ramp times
and start
voltage. See
table below.
Off
Profile no.0
5
Off
A
6
Trip class
selection
See table
below Off
Off
Trip class 5
1
Not used
2
3.2A
Off
3
1.6A
Off
4
0.8A
Off
5
0.4A
Off
1
2
3
4
5
6
1
2
3
4
5
6
OFF ON
177ha007b.10
B
6
Full load
current
setting (note:
0.1Amps is
always added
internally)
0.2A
See table
below
Off
FLC = 0.1A
Note: Settings marked grey are applicable
only in Extended versions.
■
Start/ stop profile setting
Choose the required Start/ Stop profile which is most
suited to the application. Use DIP switches A1-A4 to set
the start/stop profile. Some examples are shown below.
4
20%
40%
60%
80%
Motor voltage %
Time, sec.
Start-stop Profile no: 14
100%
8
[DIP Switch settings
A1,A2,A3:ON; A4:OFF]
7 Sec.
5 Sec.
Start ramp
Stop ramp
2
6
Run
4
20%
40%
60%
80%
Motor voltage %
Time, sec.
Start-stop Profile no: 7
177ha025.10
100%
8
[DIP Switch settings
A1:OFF; A2,A3,A4:ON]
4 Sec.
Start ramp
Coast to stop
2
6
Run
MG.05.A2.02 - VLT is a registered Danfoss trademark
9