Danfoss – 28
VUBMA102
3 .2 .7
sub-menu DeFrOsT,
DHP-A
This menu is specific to DHP-A.
In the “DEFROST” menu it is possible to view miscel-
laneous information about the defrost and also pos-
sible to make adjustments.
Menu text
Description
Adjusted by:
DEFROSTS
Total number of defrosts carried out since
installation, that is, the number not reset.
Not adjustable
BETW. 2 DEFR
The operating time of the compressor in
minutes between the 2 last defrosts.
Not adjustable
TIME SINCE
DEFROST
The operating time of the compressor in
minutes since last defrost. Reset after a
defrost is completed.
Not adjustable
FAN H OFF AT
Fan high speed is deactivated at this
outdoor temperature and low speed is
activated.
By the customer,
if necessary.
DEFROST CURVE
Here, the angle of the defrost curve can
be changed using the right-hand arrow
and by either pr or -. (Change the
start temperature for when defrosting is
to begin).
By the customer,
if necessary.
MANUEL DEFR
By using the right-hand arrow and then
pr, defrost can be started manu-
ally (20°C for 10 minutes).
By the customer,
if necessary.
DEFROST
DEFROSTS
0 S
BETW. 2 DEFR
0 M
TIME SINCE DEFROST
0 M
FAN H OFF AT
12°c
DEFROST CURVE
MANUEL DEFR
0