Parameter
Meaning
CURVE +5
Local increase or reduction of CURVE at an outdoor temperature of +5°C. Shown in the graph
for CURVE.
Factory setting: 0°C, range: -5°C – 5°C
CURVE 0
Local increase or reduction of CURVE at an outdoor temperature of 0°C. Shown in the graph
for CURVE.
Factory setting: 0°C, range: -5°C – 5°C
CURVE -5
Local increase or reduction of CURVE at an outdoor temperature of -5°C. Shown in the graph
for CURVE.
Factory setting: 0°C, range: -5°C – 5°C
DURING COOLING
During production of cooling the shunt group can be adjusted.
Factory setting: AUTO, range: AUTO, OPEN, CLOSED
CONSTANT TEMP
Controlling the shunt group against a constant temperature is an alternative to the control
using a heat curve given above. Control using constant temperature is selected using the
parameter CONSTANT TEMP in the Service menu.
Factory setting: 18°C, range: 10°C – 30°C
SETBACK TEMP
The temperature the shunt group works with when the temperature reduction is activated in
the menu CALENDAR.
Factory setting: 18°C, range: 10°C – 30°C
9.5
HOT WATER
Parameter
Meaning
HOT WATER
Allows hot water production.
Factory setting:
, range:
– ON
TOP-UP
Forced hot water production with compressor and aux. heater.
Factory setting:
, range:
– ON
9.6
COOLING
Parameter
Meaning
COOLING
Allows production of cooling.
Factory setting:
, range:
– ON
START
Temperature on the return sensor for start of cooling production.
Factory setting: 25°C, range: STOP + 5°C – MAX START TEMP
Installation instructions VMGFD102 – 49