background image

Installation Guide

Self -limiting cables on drum

Installation Guide - Self- limiting cables on drum

Intelligent solutions 

with lasting effect 

Visit DEVI.com

EN

Summary of Contents for DEVIpipeguard LSZHT

Page 1: ...Installation Guide Self limiting cables on drum Installation Guide Self limiting cables on drum Intelligent solutions with lasting effect Visit DEVI com EN ...

Page 2: ...llation guidelines 4 4 Application overview 4 5 Thermostats controllers 5 6 Accessories 6 6 1 Fixing elements 6 6 2 Connection kits 7 7 Typical installations 10 7 1 Typical pipe tracing installation 10 7 2 Typical roof protection installation 11 8 Standard compliance 12 9 Warranty 12 AN384935621519en 010101 DEVI 2 ...

Page 3: ... should be indicated by for supply piping and branch lines including sprinkler heads 3 Installation guidelines It is not recommended to install heating cables at tempera tures below 5 C Heating cable bending diameter must be at least 10 times the cable diameter to the inside of the cable Do not bend connections Free end from cold lead and kit components must be protected by installer to avoid wate...

Page 4: ...local electric regulations and connected to a residual current device RCD The DEVIreg thermostat must be commissioned as prescribed in the thermostat manual Recommended temperature setting is according to Application Guide or Installation Guide More information about thermostats and controllers can be found at www devi com Sensors Sensors can be live 230V components and must be treated according t...

Page 5: ... 1 Fixing elements DEVIclip Roof Hook For fixing cables to roofing screws UV protected DEVIclip Guard Hook For fixing cables to the snow guard and roof edge UV protected DEVIclip Relief For relieving cables hanging in downpipes Spaceclip For attaching cables and relieving from sharp edges DEVIfast Double For fixing cable loops in downpipes DEVI Aluminium Tape For ensuring efficient heat transfer 5...

Page 6: ...cting two heating cables DEVIconnecto B T Heating cable T branch as a T junction for three heating cables and 1 end terminal DEVIconnecto B TE2 Heating cable double connection with 1 5 m power cable and 2 end terminals DEVIconnecto B TE3 Heating cable T branch with 1 5 m power cable and 3 end terminals DEVIconnecto B X Heating cable X branch for 4 heating cables incl 2 end terminals DEVIconnecto B...

Page 7: ...pply assembly view heating cable DEVI EasyConnect EC 2 Power supply connection set for 2 cables ECS ECF ECM assembly view power supply heating cable DEVI EasyConnect EC 3 Power supply connection set for 3 cables heating cable end muff DEVI EasyConnect EC ETK End plug set ECF ECM assembly view end muff heating cable DEVI EasyConnect EC 1 ETK Power supply connection set with end plug 7 DEVI AN384935...

Page 8: ...Industry Picture Name Description Connection kit for DEVIpipeguard 30 60 Industry PT 30 60 heating cables With clamping block for the connection of cold lead and heating cable shrink end cap shrink tubes bitumen gaskets and ferrules Connection kit for DEVIpipeguard 30 60 Industry PT 30 60 heating cables For mounting in connection box with screw connections With cable gland M20x1 5 with locknut shr...

Page 9: ...es 5 Straight lines and sensor must be fitted as shown at Fig 2 Twisted lines are attached as shown for every approx 1 m pipe with aluminum tape 6 Apply aluminum tape below mandatory for plastic pipes and on top on the whole length of the cable Make sure that the cables do not cross sharp edges 7 Attach and cover the sensor and the tip on top of the pipe with aluminum tape Extend cold tails leads ...

Page 10: ...rs gutter valleys on the roof and or the cable 6 Install the cable s on the roof in gutters and downpipes Check once again and compare the insulation resistance 7 Install sensors and extend sensor cables cold tails terminate cables and place connec tions dry Seal all penetrations e g through roofs and walls 8 Check once again and compare the insula tion resistance The measured value shall be no le...

Page 11: ...ordance with the instructions the fault is submitted to the installer or the seller without undue delay and proof of purchase is provided Please note that theWARRANTY CERTIFICATE must be filled in stamped and signed by the author ized installer performing the installation Installation date must be indicated After the installation is performed store and keep theWARRANTY CERTIFICATE and purchase doc...

Page 12: ...ts without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies Danfoss and all Danfoss logotypes are trademarks of Danfoss A S All rights reserved Danfoss A S DEVI devi com 45 7488 8500 E Mail EH danfoss...

Reviews: