background image

ENGINEERING

TO M O R R OW

Installation guide

Colibri® Electric Expansion Valves

Type ETS 12C, ETS 24C, ETS 25C, ETS 50C, ETS 100C 

 

Colibri® Electric Regulating Valves

 

Type KVS 2C, KVS 3C KVS 5C

03

4R9

80

6

03

4R9

80

6                                            

© Danfoss | DCS (sw) | 2018.01

DKRCC.PI.VD1.F6.ML | 1 

Danfoss

R64-3051.10

Danfoss

R64-3051.10

Place the valve close to the evaporator.

It is recommended to use Danfoss filter drier before 
the expansion valve or a strainer for particles of 150 
micron or smaller.

Application ETS 

Colibri®

Flow direction

 

 

Allowable ambient temperature:

Min. -40 °C / -40 °F
Max.  70 °C / 158 °F

Max. working pressure:

50 bar(g) / 725 psi(g)

Refrigerants : 

R410A, R404A, R507, R134a, R407A, R407B, R407C, R407F, R32, R290, R1234ze, R1234yf, R449A, 

R449B, R452A, R1270, R600, R600a, R22, R23, R227, R417A, R444B, R447A, R448A, R454B, R422A, R422D, R427A, 
R502, R513A, R413A, R438A, R450A, R455B, R454C, R454A, R452B and *L40 
*

R-number allocation by ASHRAE is pending

Fluid temperature:

Min. -40 °C / -40 °F
Max.  70 °C / 158 °F

Total steps:

600 full steps

Phase current: 

800 mA peak /
600 mA RMS

Coil resistance:

10 Ω (20 °C / 68 °F)

Stepper motor type: 

Bipolar

Do not connect directly to AC/DC power source. 
Connect valve to appropriate controller/driver only. 

ETS / KVS Colibri® valves are delivered in open position, ready for brazing. 
An AST –g service driver is available for manual operation / service of ETS / KVS Colibri® valves.

English

Bi-flow

Reverse flow

Normal flow 
(Using sight glass for flash gas detection - ETS 25C to ETS 100C)
KVS Colibri® valves have no sight glass integrated

Danfoss

34G231.10

Application KVS 

Colibri®

ETS Colibri®

KVS Colibri®

Normal

Reverse

GREEN:     DRY

YELLOW:  WET

Danf

oss

34G136.12

MADE IN DENMARK

ETS XXXC

10 Ω, 800mA peak

N0311A

Colibri® Electric

Expansion valve

-40/+70°C / -40/+158°F

PS 50bar / MWP 735psig

034GXXXX

Normal

Reverse

Danf

oss

34G156.12

MADE IN DENMARK

ETS XXXC

10 Ω, 800mA peak

N0311A

Colibri® Electric

Expansion valve

-40/+70°C / -40/+158°F

PS 50bar / MWP 735psig

034GXXXX