7.3 Spare parts recommendation/accessories
7.1 Preparation
7.2 Work to be carried out
7
|
Maintenance
Oil change:
In principle, an oil change is not mandatory if the system is correctly manufactured
and operated.
However, based on decades of experience we recommend that the following oil change/service
work is carried out:
-
First oil change during the first maintenance system.
-
Then after every 10,000 – 12,000 operating hours, though no more than
3 years, cleaning oil and suction filter at the same time.
Annual checks:
Oil level, tightness, running noise, pressures, temperatures, function of auxiliary
devices such as a oil sump heater, pressure switch.
WARNING!
Before starting any work on the compressor:
Switch off the compressor and secure it to prevent a restart.
Relieve compressor of system pressure.
Prevent air from infiltrating the system!
After maintenance has been performed:
Connect safety switch.
Evacuate compressor.
Release switch lock.