Set Control Parameters

Press 

M

 button for 6 seconds to enter the parameter setting mode. Press 

M

 for parameter selection and set the 

parameter range via 

<

 or 

>

. The upper digits indicate the parameter number.  Complete all adjustments.

To exit the parameter setting mode, wait for automatic exit (30 seconds). 

The digits indicate the set value as follows:

No.

Parameter settings

Settings range

Default
WT-DM

P01 Working mode

(Will not show on the display)

01: Manual

02: Advanced Programmable Timer

NA

P02 Temperature control mode

01: Only room temp.;

02: Room and floor temp.;

03: Only floor temp.

01

P03 High room temp. limit

5-35° C (only for 01 and 02 in P02)

30° C

P04 Low room temp. limit

5-35° C (only for 01 and 02 in P02)

5° C

P05 Floor temp. limitation mode

01: High temp. limitation;

02: Low temp. limitation (only for 02 in P02)

01

P06 Floor temp. limitation setpoint

20-45° C (only for 02 in P02)

35° C

P07 High floor temp. limit

20-45° C (only for 03 in P02)

35° C

P08 Low floor temp. limit

20-45° C (only for 03 in P02)

20° C

P09 Frost protection

01: Enable; 02: Disable

01

P10 Frost protection setpoint

5-17° C

5° C

P11 Timer display option

(Will not show on the display)

01: 24 h; 02: 12 h

NA

P12 Room temp. display option at 

shutdown

01: No display current temp.;

02: Display current temp.

01

P13 MODBUS slave address

1 to 64

01

P14 MODBUS baud rate

00: 4800

01: 9600

00

P15 MODBUS parity check

00: No check

01: Odd check

02: Even check

01

P03 to P08 appear on relevant temperature control mode.

Error Messages

E1

Room sensor failure

E2

Floor sensor failure

EE

EEPROM failure

Lo

Temperature lower than 0° C

Hi

Temperature higher than 50° C

All relay output will be turned off in all cases.