Wiring and terminal tightening specifications
Terminal tightening and wire specifications for the VLT 2800 and
VLT 6000 are defined in Table I.
Total wiring length to connect up to 10 VLT 6000 and VLT 2800
drives from the BACLink portal should not exceed 3,000 feet
(900m) at 9600 baud rate.
Table I. Control Wiring and Torque
Specifications
Mounting requirements
Mount the BACLink enclosure as required using the predrilled
mounting holes (see Figure 2). The unit weighs approximately
15.3 pounds (7 kg).
For BACLink portals ordered without an enclosure, mount the unit
in an enclosed panel using the mounting holes provided on the
BACLink portal backplate (refer back to Figure 1). Leave about 2
inches (5 centimeters) on each side for wiring access. In addition,
the BACLink portal requires 24 VAC input power.
BACLink portal is a Class 2 device (less
than 30VAC, 100VA maximum). Take
appropriate isolation measures when
mounting BACLink portal in control panels
where non-Class 2 devices (for example,
120VAC) or wiring are present.
WARNING
!
11.00
[279.4]
∅
0.31
[7.9]
4 PLCS.
9.00
[228.6]
12.22
[310.4]
12.22
[310.4]
4.21
[107.0]
NOTE: Dimensions in inches [mm].
Figure 2. BACLink Enclosure Mounting Dimensions
Torque
Specification
Control Wiring
24 VAC Input Wiring
4.5 in-lbs (0.5 Nm)
18 – 24 AWG
(0.75mm
2
– 0.2mm
2
)
shielded twisted pair
22 AWG (0.3mm
2
)