Device Description
27
3.3 Technical Data
1)
Stem remains in last position
2)
Stem extends
AMV210
AMV213
AME210
AME213
Safety function
2)
-
yes
-
yes
Stroke
mm
15
Positioning time s/mm
12
Positioning force
N
300
Voltage supply
V
230 V
+10 % -15 %
,
50/
60 Hz
24 V
+10 % -15 %
,
50/60 Hz
Power consumption
VA
8
Input signal
Three-position
step signal
230 V, 50/60 Hz
0(4)–20 mA
0(2)–10 V
Output signal
–
0(2)–10 V
Behavior in case of a
drop-out
1)
2)
1)
2)
Type of protection
acc. to EN 60529
IP 54 if installed in a vertical upright position,
other installation positions: IP 52
Safety class DIN VDE 0106
II
Ambient operation
temperature
°C
-10 to +50
Ambient storage and
transportation
temperature
° C
-10 to +70
End position switch-off
Switch-off dependent on torque
Additional Equipment (cannot be added later)
End switches (2 pieces)
(only design AMV210, 213)
voltage-free, two-way switch, max. 250 V AC or
DC, 2 A resistive load, 1 A inductive load
Summary of Contents for AMV213
Page 45: ...Troubleshooting 45...