Danfoss AMV 110 NL AQT Datasheet Download Page 3

3

VD.LE.A6.02

   © Danfoss 01/2014

DEN-SMT/SI

position 
indicator

Data sheet 

Actuators for three point control AMV 110 NL, AMV 120 NL

Commissioning

The factory setting of the spindle is the fully 

stem up position because of easier mechanical 

connection of the actuator on the valve.

1.  Check the valve neck. The actuator should be 

in stem up position (factory setting). Ensure 

that the  actuator is mounted securely on the 

valve body

2.  Wire the actuator according to the

  wiring diagram

 

3.  The direction of the stem movement can be 

observed on the position indicator

Installation and 

commissioning procedure

(if required)

 

Do not touch anything on 

the PCB! 

Do not remove the cover 

before the power supply is fully 

switched off.

Manual override

(for service purposes only)

Caution:

Do not manually operate the

drive if power is connected!

Do not dismount the actuator 

from the valve when it is in a 

stem down position!

If dismounted in a stem down 

position, there is a high risk that 

the actuator gets stuck.

•  Remove cover 

•  Press and hold the button 

 (on the 

bottom side of the actuator) during manual 

override 

•  Replace cover 

•  Install actuator on valve 

Remark:

A ‘click’ sound after energising the actuator 
indicates that the gear wheel has jumped into 
normal position.