Actuator for two point control AMI 140
Data sheet
DH-SMT/SI
VD.KH.B1.02
© Danfoss 03/2008
2
Installation
Mechanical
The actuator should be mounted with the valve
stem in either horizontal position or pointing
upwards.
The actuator is fixed to the valve body by means
of a mounting ring which requires no tools for
mounting. The ring should be tightened by hand.
Electrical
Important: It is strongly recommended that the
mechanical installation is completed before the
electrical installation.
Each actuator is supplied with the connecting
cable for the controller.
Wiring
AMI 140 - 230V
AMI 140 - 24V
Commissioning
The factory setting of the spindle is the fully
stem up position because of easier mechanical
connection of the actuator on the valve.
Disposal
The actuator must be dismantled and the
elements sorted into various material groups
before disposal.
BLACK
RED
GRAY
Top view
Jumper setting
sw=OFF actuator retracted
sw=ON actuator extracted
sw=OFF actuator extracted (pushed)
sw=ON actuator retracted (pulled)
default setting for use with ABQM valve
BLUE
BLACK
BROWN
Top view
Jumper setting
sw=OFF actuator retracted
sw=ON actuator extracted
sw=OFF actuator extracted (pushed)
sw=ON actuator retracted (pulled)
default setting for use with ABQM valve
Common
Black
Bed
Gray
Common
Blue
Black
Brown