background image

Data sheet

AMI 140

Actuator for two point control

DH-SMT/SI

VD.KH.B1.02  

©  Danfoss 03/2008

1

Description 

AMI 140 is 2 point 3 wires actuator used with 

AB-QM (DN 10-32) and VZ, VZL, VRBZ valves. 

The actuator can be used with fan coil units, 

induction units, small re-heaters, re-coolers and 

zone applications in which hot/cold water is the 

controlled medium.  The actuator provides with 

factory default setting (actuators spindle fully 

stem up):

- normally closed function for AB-QM and 

- normally open function for VZ, VZL, and VRBZ 

Note: it is possible to change setting  from normally closed 
to normally open function (see “Wiring” part jumper 
setting, page 2.

Main data:

•  2-point 3 wires versions 
•  Force switch-off at stem down position 

prevents overload of actuator and valve

•  No tools required for mounting
•  Maintenance free during lifetime
•  Low noise operation
•  Supplied with 1.5 m cable.

Ordering

Type

Supply 

voltage

Speed

Code No.

AMI 140

24 V~

12 s/mm

082H8048

230 V~

082H8049

Technical data

Power supply

24 Vac, 230 Vac; +10 to –15%

Power consumption

1 VA - 24 Vac; 8 VA - 230 Vac

Frequency

50 Hz / 60 Hz

Close of force

200 N

Stroke

5.5 mm

Speed

12 s/mm

Max. medium temperature inside the pipe

130 °C

Ambient temperature

0 … 55 °C

Storage and transport temperature

–40  … +70 °C

Protection code

IP 42

Weight

0.3 kg

 - marking in accordance with standards

Low Voltage Directive 73/23/EEC, EMC-Directive 2006/95/EEC:

- EN 60730-1, EN 60730-2-14

Spare parts

Type

Code No.

Cable (5m) - 24 V

082H8052

Cable (5m) - 230 V

082H8053