Mechanical Stroke Setting
34
3. Adjust stroke indicator to 0.
4. Unscrew covering screw
1
.
5. Turn stroke limiting screw
2
to
the right up to its stop.
➻
➻
➻
➻
The stroke of the actuator is
set to 0 mm.
adjust
1
2
T1 Valve strokes VIM2, AIQM, VIS2, VIU2
Nom.
diam.
DN
15
20
25
32
40
50
VIM2
AIQM
Valve
stroke
mm
8
10
15
Turns of stroke
limiting screw
6.5
8
12
VIS2
Valve
stroke
mm
5
Turns of stroke
limiting screw
4
VIU2
Valve
stroke
mm
5
Turns of stroke
limiting screw
>
5