Default screen

•   Press   

•   Press   

•   Press   

  Enter password: 
 

                

AKS 4100

DISTANCE

5000 mm

AKS 4100

2.0.0

SUPERVISOR

AKS 4100

2.0.0

__________

AKS 4100

2.1.0

INFORMATION

AKS 4100

2.5.0

APLICATION

AKS 4100

2.5.1

TRACING VEL.

•   Press   4 times. 

•   Press   

•   Press   2 times. 

•   Press   to check/change GAS EPS.R. 

  (Select the correct value from the tables  

  below and on page 8) 

 Press   to change cursor- 

 position. 
  Press   to decrease the value or   to 

  increase the value.

 

AKS 4100

2.5.3

GAS EPS. R

AKS 4100

GAS EPS. R

1.066

AKS 4100

2.5.3

GAS EPS. R

AKS 4100

1.0.0

STORE NO

AKS 4100

DISTANCE

5000 mm

•   Press   to confirm.

•   Press   3 times.

•   Press   or   to select between  

  STORE NO or STORE YES.  

  Select STORE YES by pressing   

 

Default screen appears:

  Entering the dielectric constant of  

  refrigerant gas completed

How to enter dielectric constant of refrigerant gas (all values below are only examples)

Optional Procedure

If the temperature condition in the stand pipe is known, a constant (dielectric constant of the refrigerant gas) 

can be

 entered (parameter 

2.5.3 GAS EPS.R), in order to obtain lower Top and Bottom Dead Zone values 

(see fig. 5)

.

Temperature 

[°C]

Temperature 

[°F]

Dielectric constant 

of refrigerant gas

Parameter 2.5.3 

GAS EPS.R

–40 

 –18

 –40.0 

 0

1.01

 –17 

 –5  

 23

1.02

 –4 

 4 

24 

 39

1.03

 12

40 

 54

1.04

13 

 18

55 

 64

1.05

19 

 24

65 

 75

1.06

25 

 28

76 

 82

1.07

29 

 33

83 

 91

1.08

34 

 37

92 

 99

1.09

38 

 40

100 

 104

1.10

41 

 44

105 

 111

1.11

45 

 47

112 

 117

1.12

48 

 50

118 

 122

1.13

R717 (NH

3

)

Temperature range:

–40°C 

 +50°C (–40°F 

 +122°F)

Temperature 

[°C]

Temperature 

[°F]

Dielectric constant 

of refrigerant gas

Parameter 2.5.3 

GAS EPS.R

 –50.0 

 –42.0   

 –58.0 

 –43 

1.01

 –41.0 

 –28.0   

 –42 

 –18    

1.02

 –27.0 

 –17.0  

 –17 

 2  

1.03

 –16.0 

 –9.0   

 16

1.04

 –8.0 

 –3.0  

17 

 27

1.05

 –2.0 

 2 

28 

 36

1.06

 7

37 

 45

1.07

 11

46 

 52

1.08

12 

 14

53 

 58

1.09

15

59

1.10

R744 (CO

2

)

Temperature range:

–50°C 

 +15°C (–58°F 

 +59°F)

Temperature 

[°C]

Temperature 

[°F]

Dielectric constant 

of refrigerant gas

Parameter 2.5.3 

GAS EPS.R

 –50 

 –25.0  

 –58 

 –13 

1.00

 –24 

 –10 

 –12 

 14 

1.02

 –9 

 0  

15 

 32

1.03

 8

33 

 46

1.04

 15

47 

 59

1.05

16 

 21

60 

 70

1.06

22 

 26

71 

 79

1.07

27 

 31

80 

 88

1.08

32 

 35

89 

 95

1.09

36 

 39

96 

 102

1.10

40 

 42

103 

 108

1.11

43 

 45

109 

 113

1.12

46 

 48

114 

 118

1.13

R22

Temperature range:

–50°C 

 +48°C (–58°F 

 +118°F)

Temperature 

[°C]

Temperature 

[°F]

Dielectric constant 

of refrigerant gas

Parameter 2.5.3 

GAS EPS.R

 –40.0 

 –18  

 –40 

 –0  

1.01

 –17 

 –4 

 25

1.02

 –3 

 5 

26 

 41

1.03

 13

42 

 56

1.04

14 

 20

57 

 68

1.05

21 

 25

69 

 77

1.06

26 

 30

78 

 86

1.07

31 

 34

87 

 94

1.08

35 

 38

95 

 100

1.09

39 

 42

101 

 108

1.10

43 

 45

109 

 113

1.11

46 

 48

114 

 119

1.12

49 

 50

120 

 122

1.13

R134a

Temperature range:

–40°C 

 +50°C (–40°F 

 +122°F)

Saturated vapour dielectric constant (default value: 1.066)

AKS 4100

1.0.0

QUICK START

AKS 4100

QUICK SETUP ?

YES                                           NO

Summary of Contents for AKS 4100

Page 1: ...7 0 m m 2 7 6 i n 2 i n p i p e 4 5 m m 1 7 7 i n Standpipe Columm 2 in pipe 3 in pipe 4 in pipe Inner diameter 52 mm 2 05 in 78 mm 3 07 in 102 mm 4 02 in Total length of guided blades after cutting 4...

Page 2: ...ge Bottom dead zone mm in mm in Ammonia HFC HCFC 800 31 5 115 4 2 801 999 31 5 39 120 4 7 1000 1999 39 79 150 5 9 2000 2999 79 118 180 7 1 3000 3999 118 157 210 8 3 4000 5000 157 197 240 9 4 Improved...

Page 3: ...U AKS 41 41U with a c supply to AKS 4100 4100U with d c supply Danfoss EKC 347 or PLC 24V a c L 24V a c N AKS 41 41U 4 20 mA Danfoss EKC 347 or PLC 24V d c 24V d c AKS 4100 4100U Danfoss M84H0018_1 24...

Page 4: ...o DISTANCE the displayed value will be the distance from the Reference point to the top surface of the liquid refrige rant see fig 5 LEVEL is display option If the display is set to LEVEL then the val...

Page 5: ...data Spacebelowcounterweight 20mm 0 8in Steel wire insertion length in counterweight 12 mm 0 5 in counterweight height 33 mm 1 3 in Max Probe length Standpipe inner length Space below counterweight 2...

Page 6: ...S 4100 1 0 0 STORE NO AKS 4100 DISTANCE 5000 mm Press to confirm Press or to select either STORE NO or STORE YES Press to confirm Default screen appears Quick Setup completed You have the possibility...

Page 7: ...40 0 0 1 01 17 5 1 23 1 02 4 4 24 39 1 03 5 12 40 54 1 04 13 18 55 64 1 05 19 24 65 75 1 06 25 28 76 82 1 07 29 33 83 91 1 08 34 37 92 99 1 09 38 40 100 104 1 10 41 44 105 111 1 11 45 47 112 117 1 12...

Page 8: ...0 DISTANCE 5000 mm AKS 4100 1 0 0 QUICK START AKS 4100 2 0 0 SUPERVISOR AKS 4100 2 0 0 __________ AKS 4100 2 1 0 INFORMATION AKS 4100 DISTANCE 5000 mm Enter password Press 6 times Press Press Press or...

Reviews: