AKD 2800
5. The frequency converter automatically undertakes
a test of the control card.
If the frequency converter displays a fault code from
37-45, the control card test has failed. Change the
control card to start up the frequency converter.
If the frequency converter comes into Display mode,
the test is OK. Remove the test connector and
the frequency converter is ready for operation.
Parameter 620
Operating mode
is automatically
set to
Normal operation
[0].
Initialisation
[3] is selected if you wish to use
the unit
’
s factory setting.
Procedure for initialisation:
1. Select
Initialisation
[3].
2. Disconnect the mains voltage and wait until the
light in the display has disappeared.
3. Connect the mains voltage.
4. An initialisation is performed in all parameters
in all Setups, with the exception of parameters
500
Address
, 501
Baudrate
, 600-605
Operating
data
and 615-617
Fault log
.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.28.H2.02 -
44