Danfoss AK-SC255 Troubleshooting Manual Download Page 6

AK-SC255 

 

 

Troubleshooting Guide

USCO.EI.RF0.D1.22 / 521U0152 

 

©Danfoss (USCO / MKS), 04- 2010

For Danfoss Technical Support call +1-410-931-8716.

Won’t Power up

Check for incoming power at MK1 connector.

• 

Check fuse at F1 (Fig. 6).

• 

Check for input power at the base of the power supply.

• 

Check for 5vdc between MH5 and MH6 on the 255PROGBD (the yellow 5v in 

• 

LED and the green 5v out should be lit.

Receiving error message(s)

Contact Danfoss Technical Support to resolve source and resolution of your 

• 

particular error messages.

Database History isn’t available or 
is lost

Insure that the battery jumper at JP5 on the base board (Fig. 7) is set on the 

• 

right two pins (this is the enabled position).
Check to see that there is a valid database with history configured.

• 

Check to see that history status is Collecting and not Suspended

• 

See if you can access history retrieval via the keypad via the AKA65

• 

If you can still not access history contact Danfoss Technical Support for further 

• 

options. 

Clock doesn’t work

Insure that the battery jumper at JP5 on the base board (see Fig. 7) is set on 

• 

the right two pins (this is the enabled position).
Now try resetting the correct date and time.  Observe this new time for several 

• 

minutes. 
If, after several minutes, the clock appears to be correct you have most likely 

• 

corrected the perceived problem. 
If, after a short time, the date returns to 01/31/95 and the clock to 00:00:00…

• 

call Danfoss Technical Support for further assistance. 

EDF Message

The most common EDF message is one saying “Could not Load…,” this usually 

• 

implies that the necessary EDF was not in the correct directory or folder. Make 
sure the EDF mentioned in the error message is in your list of EDF’s.
Remember, after loading EDF’s or a Device List you must reset the AK-SC255.

• 

If your problem is still not resolved, call Danfoss Technical Support for 

• 

assistance..

Figure 7

1.0 Amp 250V
fuse on the “hot leg”
of input power 

Figure 6

Summary of Contents for AK-SC255

Page 1: ...REFRIGERATION AIR CONDITIONING MAKING MODERN LIVING POSSIBLE AK SC255 Troubleshooting Guide Troubleshooting Guide...

Page 2: ...h the AK_SC255 4 Will not scan scanning issues 4 I O network failure 4 License error 5 Lost license 5 Screen Display Issues 5 World map doesn t disappear 5 Won t power up 6 Receiving error message s 6...

Page 3: ...th screw terminals Fig 1 or plug in connections Fig 2 Check that to see that the CPU card Fig 3 is firmly in place If found to be unevenly seated press firmly on its corners until it no longer moves F...

Page 4: ...h Danfoss Technical Support for other options before replacing the suspect module Will not scan Scanning Issues Check that all Comm Modules and associated I O are powered on and are addressed as confi...

Page 5: ...Most likely after performing the checks at the top of page 2 issues with a white screen or a flickering screen will have been resolved If the flickering re occurs note if the red black twisted pair wh...

Page 6: ...ia the keypad via the AKA65 If you can still not access history contact Danfoss Technical Support for further options Clock doesn t work Insure that the battery jumper at JP5 on the base board see Fig...

Page 7: ...t setting this feature up you may need to reset the unit for the new setting to take effect If none of these things has helped call Danfoss Technical Support for further assistance Web Browser Issues...

Page 8: ...USCO EI RF0 D1 22 521U0152 Danfoss USCO MKS 04 2010 For Danfoss Technical Support call 1 410 931 8716 www danfoss us...

Reviews: