Service Guide   RC8BV402  ©  Danfoss  2016-02 

AK-CH 650 Version 2.0x

 

--Zone delay s 

Time delay between step cut-outs in the regulation band under the “-Zone band”

 

 

Set in seconds.

 

Kp S4 

Amplification factor for P0 regulation

 

Night offset K 

Displacement value for suction pressure in connection with an active night

 

 

setback signal (set in Kelvin)

 

Tref S3 offset 

Reference temperature for the temperature signal S3, i.e. when = Tref, there is no    

 

 

displacement of the reference.

 

K1 S3 offset 

Displacement of the reference for the charge temperature S4 on an increase in S3    

 

 

temperature in relation to ”Tref S3 offset” of 1°C (K1 = 0 gives no displacement)

 

Max.Reference °C 

Max. permissible suction pressure reference

 

Min.Reference °C 

Min. permissible suction pressure reference

 

VSD Min. speed Hz 

Minimum allowed speed before stop of Variable Speed drive (Low load condition)

 

VSD Start speed Hz 

Minimum speed for start of Variable speed drive (Must be set higher than    

 

 

 

“VSD Min. Speed Hz”)

 

VSD Max. speed Hz 

Highest permissible speed for the compressor motor

 

Load shed limit 1 

Set max capacity limit for load shed input 1

 

Load shed limit 2 

Set max capacity limit for load shed input 2

 

Override limit Po 

Set max load shedding override limit for suction pressure Po

 

Override delay 1 min 

Override delay for load shed limit 1. If the suction pressure exceeds 

“Override limit Po” during load shedding and the set delay has expired, the load shed 

limit 1 will be cancelled

 

Override delay 2 min 

Override delay for load shed limit 2. If the suction pressure exceeds 

“Override limit Po” during load shedding and the set delay has expired, the load shed 

limit 2 will be cancelled

 

Po pump down limit °C 

Set the actual pump down limit for the last compressor

 

Initial start time 

The time after start-up where the cut-in capacity is limited to the first compressor step.

 

1 comp. start delay 

On new start the start of the first compressor is delayed by the set delay time so that the  

 

 

brine pumps can bring the brine up to speed before start of the first compressor.

 

Extra cooling mode 

A relay is reserved and it will be activated if the brine temperature is higher than  

 

  

desired.

 

Extra cooling offset 

Set the value (K above the reference) where the relay is to activated

 

Extra cooling delay 

Delay time before the relay can be active. The time applies during normal regulation

 

Extra cooling init d. 

Delay time before the relay can be active. The time applies during cooling after start-up  

 

 

and after defrosting. 

Suction compressor status

Measurements 

AK error 

When “ON”, the controller is in alarm condition.

 

Comp. Ctrl. temp. 

Actual temperature for compressor control

 

S4 Cold brine supply 

Actual  cold brine supply temperature measured with S4 temp. sensor

 

S3  Cold brine return 

Actual  cold brine return temperature measured with S3 temp. sensor

 

P0 °C 

Suction pressure in °C.  (Measured with the pressure transmitter)

 

Comp. ctrl. Ref. °C 

Actual reference temperature for compressor control

 

Compressor cap. % 

Cut-in compressor capacity in % (of total capacity)

 

Request Comp. Cap % 

Reference for compressor capacity (deviations may be due to time delays)

 

Cond. ctrl. temp °C 

Actual temperature for control sensor (Pc or S7)

 

S7 warm brine °C 

Actual warm brine temperature for S7 media sensor

 

 

(Only used if S7 sensor is selected as regulation sensor)

 

Pc °C 

Condensing pressure in °C. (measured with the pressure transmitter)

 

Cond. ctrl. ref. °C 

Actual reference temp. for condenser capacity 

 

 

(incl. external reference signal, if any)

 

Cond. cap.  % 

Cut-in condenser capacity in % (of total capacity)

 

Request Cond. cap % 

Reference for condenser capacity

 

VSD 1 safety 

Status on safety input for variable speed controller on compressor 1

 

 

ON: Alarm 

 

 

OFF: No alarm

 

VSD 2 safety 

Status on safety input for variable speed controller on compressor 2

 

 

ON: Alarm 

 

 

OFF: No alarm

 

Comp. 1 Status 

0: Power up   

Controller has been powered up/Compressor is not used  

 

 

 

1: Stopped   

Compressor hat been stopped

 

 

2: Manual 

Compressor capacity is controlled manually

 

 

3: Alarm 

Compressor is in alarm condition (cut out on safety)

 

 

4: Restart 

Compressor is waiting for elapse of “Recycle time”

 

 

5: Standby 

Compressor is ready to start

 

 

10: Full loaded   All capacity cutin

 

 

11: Running 

Capacity control is running

Summary of Contents for AK-CH 650

Page 1: ...Capacity controller for water chiller AK CH 650 Service Guide ADAP KOOL Refrigeration control systems...

Page 2: ...ritten out They can only be made from the Service Tool programme There are four kinds of settings ON OFF settings settings with a variable value time settings and reset alarms Enter the new value or m...

Page 3: ...Read the next section Documentation Documentation Documentation of the settings of the individual controllers can be made with the print function in the AKM programme Select the controller for which...

Page 4: ...details about the predefined applications Refrigerant type Po Select refrigerant type 0 not selected 1 R12 2 R22 3 R134a 4 R502 5 R717 6 R13 7 R13b1 8 R23 9 R500 10 R503 11 R114 12 R142b 13 User defi...

Page 5: ...make the best possible fit to actual load 0 Sequential 2 Cyclic 3 Best fit S4 Min 24h Minimum value for S4 temp For the last 24 hours S4 Max 24h Maximum value for S4 temp For the last 24 hours S4 Aver...

Page 6: ...e start of the first compressor Extra cooling mode A relay is reserved and it will be activated if the brine temperature is higher than desired Extra cooling offset Set the value K above the reference...

Page 7: ...in compressor capacity in of total capacity Request Comp Cap Reference for compressor capacity deviations may be due to time delays Cond ctrl temp C Actual temperature for control sensor Pc or S7 S7...

Page 8: ...t stop the defrost is stopped when the temperature of the selected defrost sensor reached the set value Max defrost time Max permitted defrosting time in minutes security time for stop using temperatu...

Page 9: ...AUTO The capacity is controlled by the PI controller Manual capacity Manual setting of condenser capacity The value is in of total capacity controlled by the controller Reference mode 0 Set point Refe...

Page 10: ...n Actual cold brine return temperature measured with S3 temp sensor P0 C Suction pressure in C Measured with the pressure transmitter Comp ctrl Ref C Actual reference temperature for compressor contro...

Page 11: ...be due to time delays Cond ctrl temp C Actual temperature for control sensor Pc or S7 S7 warm brine C Actual warm brine temperature for S7 media sensor Only used if S7 sensor is selected as regulatio...

Page 12: ...age inputs Measurements AK error When ON the controller is in alarm condition Comp Ctrl temp Actual temperature for compressor control S4 Cold brine supply Actual cold brine supply temperature measure...

Page 13: ...y mode Regulation has stopped Low P0 Minimum safety limit for suction pressure P0 has been violated High S4 High alarm limit for S4 has been exceeded Low S4 Low alarm limit for S4 has been exceeded Hi...

Page 14: ...nfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary i...

Reviews: