Figure 46: SET button parameter list
(PS)
<
r12
<
o61
r--
o03
A--
r89
c--
r00
r15
r61
A36
o17
d--
o30
n--
o20
F--
o21
t--
d01
h--
d03
o--
d10
p--
d04
q--
d02
u--
<
<
SET
SET
cFg
Set
Danf
oss
84B8272
SET button,
3 s: Configuration settings
PS: Password (if any)
Main switch
M
enu g
roups
See also the f
ollo
wing pages
.
Application
MODBUS address
Food type
Cut-out temperature
Ther. sensor S4 %
Ther. sensor S4% night
Alarm sensor S4%
Display air S4%
Refrigerant type
Min. transmitter range
Max. transmitter range
Defrost method
Defrost interval
Defrost sensor
Max. defrost time
Defrost stop temperature
(Return)
(Return)
<
Inf
StA
SET
App
SET
in
SET
AI1
(PE)
out
SET
do1
*
AI2
**
buS
SET
do2
*
AI3
**
SoF
SET
do3
*
AI4
**
<
do4
*
Ao1
AI5
**
<
di1
**
di2
**
**
<
Danf
oss
84B3292
Info button,
3 s: Information for service use
See control state message
See selected application
Output status
When you want info on a relay
output, the dot will show whether
the relay is activated (energized)
for e.g.:
do4 = not activated
do.4 = activated
MODBUS quality
See SW version
(Return)
(Return)
(Return)
Read output status
Read input status
*
**
StA
The output's function (determined at
configuration). DOs and AOs can also be forced
controlled from this menu, when r12 Main switch
has been set to position "service". Forced control of
a function can also be performed in codes q11 to
q27.
The input's function (determined at configuration)
See control state message in
1.
2.
3.
4.
5.
Parameter groups when operating via display
Figure 47: Info button parameter list
Get a good start
With the following procedure you can start regulation very quickly:
Open parameter r12 and stop the regulation (in a new and not previously set unit, r12 will already be set to 0
which means stopped regulation.)
Select application based on the wiring diagrams (see
Application set-ups and IO connections
)
Open parameter o61 and set the application number
For network. Set the address in o03
Then select a set of presets from the "Food type" help table
© Danfoss | Climate Solutions | 2022.08
BC365212986197en-000201 | 35
AK-CC55 Compact