90
RS8GM222 © Danfoss 10-2014
AK-CC 750 - 080Z0130 & 080Z0139
Function
The controller has a setting where you can
choose between various types of installation. If
you use these settings, the controller will suggest
a series of connection points for the different
functions. These points are shown below.
Even if your installation is not 100% as described
below, you can still use the function. After use,
you need only adjust the divergent settings.
The given connection points in the controller can
be changed if you wish.
Appendix - Recommended
connection
Comments
Quick Setup IO Assignments
1
4 Case
LnUp LT C
AI Points (Base Module)
1-1
1-2
1-3
1-4
1-5
1-6
1-7
1-8
1-9
1-10
1-11
Disc Air A
Disc Air B
Disc Air C
Disc Air D
Def Term A
Def Term B
Def Term C
Def Term D
Door Sw
DO Points (Base Module)
Power Module Connector
1-12
1-13
1-14
1-15
1-16
1-17
1-18
1-19
1-20
1-21
1-22
1-23
Sol Valve
ASH
Light
Def
Fan
2
4 Case
LnUp MT C
AI Points (Base Module)
1-1
1-2
1-3
1-4
1-5
1-6
1-7
1-8
1-9
1-10
1-11
Disc Air A
Disc Air B
Disc Air C
Disc Air D
Door Sw
DO Points (Base Module)
Power Module Connector
1-12
1-13
1-14
1-15
1-16
1-17
1-18
1-19
1-20
1-21
1-22
1-23
Valve A
ASH
Light
Def
Fan
3
4 EEV LT
AI Points (Base Module)
AI Point (Expansion Module)
1-1
1-2
1-3
1-4
1-5
1-6
1-7
1-8
1-9
1-10
1-11
2-1
2-2
2-3
2-4
2-5
2-6
2-7
2-8
Disc Air A
Evap Out A
Def Term A
Disc Air B
Evap Out B
Def Term B
Disc Air C
Evap Out C
Def Term C
PE Pressure
Door Sw
Disc Air D
Evap Out D
Def Term D
Dual-Temp
DO Points (Base Module)
DO Point (Expansion Module)
1-12
1-13
1-14
1-15
1-16
1-17
1-18
1-19
2-9
2-10
2-11
2-12
2-13
2-14
2-15
2-16
EEV A
EEV B
EEV C
EEV D
Fan
Light
Def
ASH
4
4 EEV LT I
Term
AI Points (Base Module)
AI Point (Expansion Module)
1-1
1-2
1-3
1-4
1-5
1-6
1-7
1-8
1-9
1-10
1-11
2-1
2-2
2-3
2-4
2-5
2-6
2-7
2-8
Disc Air A
Evap Out A
Def Term A
Disc Air B
Evap Out B
Def Term B
Disc Air C
Evap Out C
Def Term C
PE Pressure
Door Sw
Disc Air D
Evap Out D
Def Term D
DO Points (Base Module)
DO Point (Expansion Module)
1-12
1-13
1-14
1-15
1-16
1-17
1-18
1-19
2-9
2-10
2-11
2-12
2-13
2-14
2-15
2-16
EEV A
EEV B
EEV C
EEV D
Fan
Light
Def
ASH
Def B
Def C
Def D
5
Uncon-
nected DOs
(OK)
4 EEV LT
NoTerm
AI Points (Base Module)
1-1
1-2
1-3
1-4
1-5
1-6
1-7
1-8
1-9
1-10
1-11
Disc Air A
Evap Out A
Disc Air B
Evap Out B
Disc Air C
Evap Out C
Disc Air D
Evap Out D
Dual Temp
PE Pressure
Door Sw
DO Points (Base Module)
1-12
1-13
1-14
1-15
1-16
1-17
1-18
1-19
EEV A
EEV B
EEV C
EEV D
Fan
Light
Def
ASH
6
4 EEV LT C
Term DI
AI Points (Base Module)
AI Point (Expansion Module)
1-1
1-2
1-3
1-4
1-5
1-6
1-7
1-8
1-9
1-10
1-11
2-1
2-2
2-3
2-4
2-5
2-6
2-7
2-8
Disc Air A
Evap Out A
DI Term A
Disc Air B
Evap Out B
DI Term B
Disc Air C
Evap Out C
DI Term C
PE Pressure
Door Sw
Disc Air D
Evap Out D
DI Term D
Dual-Temp
DO Points (Base Module)
DO Point (Expansion Module)
1-12
1-13
1-14
1-15
1-16
1-17
1-18
1-19
2-9
2-10
2-11
2-12
2-13
2-14
2-15
2-16
EEV A
EEV B
EEV C
EEV D
Fan
Light
Def
ASH
7
4 EEV LT I
Term DI
AI Points (Base Module)
AI Point (Expansion Module)
1-1
1-2
1-3
1-4
1-5
1-6
1-7
1-8
1-9
1-10
1-11
2-1
2-2
2-3
2-4
2-5
2-6
2-7
2-8
Disc Air A
Evap Out A
DI Term A
Disc Air B
Evap Out B
DI Term B
Disc Air C
Evap Out C
DI Term C
PE Pressure
Door Sw
Disc Air D
Evap Out D
DI Term D
Dual-Temp
DO Points (Base Module)
DO Point (Expansion Module)
1-12
1-13
1-14
1-15
1-16
1-17
1-18
1-19
2-9
2-10
2-11
2-12
2-13
2-14
2-15
2-16
EEV A
EEV B
EEV C
EEV D
Fan
Light
Def A
ASH
Def B
Def C
Def D
Descriptions:
'EEV' = electronic expansion valve
'LLSV' = liquid line solenoid valve
'LT' = low temp
'MT' = medium temp
'LnUp' = Line Up
'I Term' = individual termination (sensor)
'C Term' = common termination (sensor)
'I Term DI' = individual termination, digital input
'C Term DI' = common termination, digital input
'CPM' = case power module
'Comm Term' = common termination (sensor)
'Ind Term' = individual termination (sensor)
'AD C Term' = adaptive defrost, common termination
(sensor)
'AD I Term' = adaptive defrost, individual termination
(sensor)
'DT C Term' = dual temp, common termination (sensor)
'DT I Term' = dual temp, individual termination (sensor)