AHF 005/010
All about VLT 8000
AQUA
■
Power wiring size
Power wiring size
Enclosure
Max. cable size, in
2
(mm
2
)
Type
Nom. Fix Torque
B
0.025 (16)
Connector
1.5 ft-lb (2 Nm)
C and D
0.078 (50)
Connector
4.4 ft-lb (6 Nm)
E, F, G and H
Bus Bars
18 ft-lb (25 Nm)
Overheat contactor (copper)
Enclosure
Max. cable size, in
2
(mm
2
)
Type
Nom. Fix Torque
0.0062 (4)
Connector
0.4 ft-lb (0.6 Nm)
Capacitor disconnect (copper)
Enclosure
Max. cable size, in
2
(mm
2
)
Type
Nom. Fix Torque
B
0.0062 (4)
Connector
0.4 ft-lb (0.6 Nm)
C and D
0.025 (16)
Connector
1.5 ft-lb (2 Nm)
E, F, G and H
0.078 (50)
Connector
4.4 ft-lb (6 Nm)
*Power wiring used for connecting the filter AHF 005
and AHF 010 in enclosure size E, F and G must
be terminated with cable lugs that can be attached
to the input and output bus bars terminals. This
type of termination imposes no specifications on
the minimum and maximum cable size suitable for
connection. Power terminal details regarding the bus
bars can be found in the figures below.
Frame E
Frame F
Frame G, Frame H
NOTE
For UL approval, use copper conductor only.
■
Operation on different line type
Line type
Operation of the filter module
TN
Directly grounded star point
Allowed
TN
Indirectly grounded star point
Allowed
IT
Isolated star point
Allowed
MG.80.B4.22 - VLT is a registered Danfoss trademark
17