42
Capacity
controller RS8GN202 © Danfoss 11-2013
AK-PC 783
Supply voltage
Supply voltage is only connected to the controller module. The
supply to the other modules is transmitted via the plug between
the modules.
The supply must be 24 V +/-20%. One power supply must be used
for each controller. The power supply must be a class II.
The 24 V must not be shared by other controllers or units. The
analog inputs and outputs are
not
galvanically separated from the
supply.
The + and – 24V input must
not
be earthed.
If using stepper motor valves, the supply for these must be pro-
vided from a separate power supply.
For CO2 facilities, it will also be necessary to safeguard the voltage
to the controller and valves using UPS.
Power supply size
The power consumption grows with the number of modules used:
Module
Type
Number á
Effect
Controller
1 x 8 =
8 VA
Extension module
200 series
_ x 5 =
__ VA
Extension module
100 series
_ x 2 =
__ VA
Total
___
VA
12
Example continued:
Controller module
8 VA
+ 2 extension modules in 200 series 10 VA
+ 2 extension modules in 100 series 4 VA
------
Power supply size (least)
22 VA