18
User
Guide RS8GY302 © Danfoss 2015-06
AK-PC
551
Quick setup
Quick configurations
This setting will reserve inputs and outputs for the following compressors and fans:
The various connections are shown on the next page.
App. no. Display
Suction group A
Suction group
B
Condenser
Speed
Digital
(Scroll / steam)
1-step
1-step
Step
Speed
17
3CDA + 2CB + FS
1
2
2
x
16
2CDA + 2CB + 3F
1
1
2
3
15
3CSA + 2CB + FS
1
2
2
x
14
2CSA + 2CB + 3F
1
1
2
3
13
4CA + 3CB + FS
4
3
x
12
3CA + 2CB + FS
3
2
x
11
2CA + 2CB + 3F
2
2
3
10
4CDA + FS
1
3
x
9
3CDA + FS
1
2
x
8
3CDA + 3F
1
2
3
7
2CDA + 2F
1
1
2
6
4CSA + FS
1
3
x
5
4CA + FS
4
x
4
4CA + 4F
4
4
3
3CSA + FS
1
2
x
2
3CA + FS
3
x
1
3CA + 3 F
3
3
0
None
After making a selection, the setting will return to “None”
After making a selection you must:
1. Set the type of refrigerant
2. Check the types of pressure transmitters
3. Check the min. and max. settings on the pressure transmitters
Factory setting:
Po A/B = AKS 32R, min=-1.0 bar, max.=12 bar
Pc = AKS 32R, min. = -1.0 bar, max. = 34 bar
SdA = NTC 86K
Setup Wizard
This wizard will lead you through the necessary settings, i.e. a total of approximately
20 to 35 display screens, depending on what is selected along the way.
The selection will also result in a connection to a given input and output. You yourself
will see this connection in the IO configuration menu. If applicable, see page 20.