Danfoss 176F6619 Installation Instructions Download Page 2

WARNING

INTERNAL FAILURE HAZARD

Under certain circumstances, an internal failure can cause a
component to explode. Failure to keep the drive enclosure
closed and properly secured can cause death or serious
injury.

Do not operate the drive with the door open or
panels off, even when the mains shield is installed.

Ensure that the enclosure is properly closed and
secured during operation of the drive.

Installation Instructions

Assembling Mains Shield

The mains shield for E1h and E2h drives is a 2-part shield. The
upper shield is installed above the air baffle, and the lower
shield is installed just below the air baffle. To install the mains
shield, use the following steps. Refer to 

Illustration 1.1

 and

Illustration 1.2

.

1.

Remove the protective plastic film from the front and
back of the upper mains shield and lower mains
shield.

2.

Remove 14 brackets from the front edges of the
drive enclosure by removing 1 screw from each
bracket. See 

Illustration 1.1

.

3.

Install 14 new brackets from the mains shield kit.
Secure the new brackets to the drive enclosure using
14 M5x12mm screws (T25) from the kit. Tighten to
2.3 Nm (20 in-lb).

4.

Feed the LCP (local control panel) cable through the
cable access hole in the upper shield. Refer to

Illustration 1.2

.

5.

Position the upper shield over the screw holes on the
brackets above the air baffle.

6.

Using 4 M5x12mm screws (T25) from the kit, loosely
tighten the upper mains shield to the brackets.

7.

If present, feed the optional USB cable through the
cable access hole in the lower shield. Position the

lower shield over the screw holes in the brackets
below the air baffle.

8.

Using 10 M5x12mm screws (T25) from the kit, loosely
tighten the lower mains shield to the brackets.

9.

Torque all mains shield fasteners to 2.3 Nm (20 in-lb).

1

Old  brackets

2

New  brackets  from  mains  shield  kit

Illustration 1.1 Mains Shield Bracket Locations

Installation Instructions

Mains Shield Kit for E1h/E2h Drives
VLT

®

 Series FC 102, FC 103, FC 202, and FC 302

2

Danfoss A/S © 08/2017 All rights reserved.

MI35I102