Creating Vent Openings in the Mounting Backplate
Refer to
Illustration 1.4
for the following steps.
1.
Cut out the intake openings in the mounting backplate. The openings must match to the intake vent openings of the
drive module.
2.
Drill the 12 screw holes around the vent openings and insert the 12 M6 X 12 pem studs, with the studs facing toward the
back of the mounting backplate.
3.
Drill the 8 screw holes to mount the drive modules and install 8 M10 pem nuts on the back side of the mounting
backplate.
Illustration 1.4 Vent Dimensions for Mounting Backplate
Installation Instructions
In-back/Out-top Cooling Kit for VLT
®
Parallel Drive Modules
VLT
®
Series FC 102, FC 202, and FC 302
MI92K102