Installation 

 MCD 

Remote 

Operator 

 

MG.17.E5.02 - VLT

®

 is a registered Danfoss trademark 

2.

 

Installation 

This section describes how to install the Remote Operator for basic control and monitoring of a soft 
starter. The Remote Operator is pre-configured to control a soft starter once control supply power is 
applied to both devices.  For basic operation, no parameter adjustments are required on the Remote 
Operator or the soft starter.  

In order to use the Remote Operator's 4-20 mA analog output to monitor motor current, follow the 
instructions in the section 4-20 mA Analog Output. 

2.1.

 

Mounting 

The Remote Operator is rated IP54 or NEMA 12   when mounted correctly in accordance with these 
instructions. It is intended for use on the flat surface of a panel, with all external wiring connected from 
behind the panel. 

The Remote Operator is supplied with a mounting bracket and four fasteners. The built-in gasket seal 
guarantees protection from outside the panel. 

Select the panel location of the Remote Operator. The required panel cutout is 92 mm x 92 mm. Place 
the Remote Operator through the cutout and locate the mounting bracket at the rear of the panel onto 
the four studs. Use the four fasteners to tighten the mounting bracket up to the rear of the panel. 

 For use on a flat surface of a NEMA 1 or NEMA 12 enclosure. 

177HA3

74.

11

Fasteners (x 4)

Mounting bracket

Universal panel cutout

(92 mm x 92 mm)

Remote Operator

 

2.2.

 

Connection 

The Remote Operator requires a minimum of three electrical connections - the external power supply, 
the chassis earth and the RS485 Starter port. All external wiring, except the chassis earth (M4 stud 
provided), is connected to spring operated clamp connector terminals with a maximum wire size of 
2.5 mm

2

. No special tools are required. 

Once the Remote Operator is mounted, connect it to the starter as illustrated. 

2.3.

 

Grounding and Shielding 

Twisted pair data cable with earth shield is recommended. The cable shield should be connected to the 
GND device terminal at both ends and one point of the site protective earth. 

2.4.

 

Termination Resistors 

In long cable runs prone to excessive noise interference, termination resistors should be installed 
between the data lines at both ends of the RS485 cable. This resistance should match the cable 
impedance (typically 120 

). Do not use wire wound resistors. 

Summary of Contents for 175G3061

Page 1: ...actice for RS485 communications when installing and using this equipment 1 2 General Description The Remote Operator can be used with MCD 200 MCD 3000 and MCD 500 soft starters and offers the followin...

Page 2: ...Remote Operator through the cutout and locate the mounting bracket at the rear of the panel onto the four studs Use the four fasteners to tighten the mounting bracket up to the rear of the panel For u...

Page 3: ...177HA264 11 Remove mains and control voltage from the soft starter before attaching or removing accessories Failure to do so may damage the equipment Once the Remote Operator Module has been installed...

Page 4: ...lows 1 Protocol AP ASCII 2 Address 20 3 Baud Rate 9600 4 Parity No parity 5 Timeout No timeout 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 16 8 4 2 1 0 0 0 0 0 DIP SWITCH A DIP SWITCH B 177HA543 10 1 2 3 4 5 4 Appl...

Page 5: ...starter 177HA375 10 MCD 3000 REMOTE OPERATOR RS485 SERIAL PORT 68 61 69 B1 B2 B3 B6 B7 B8 GND RS485 STARTER RS485 NETWORK 4 20 mA ANALOGUE OUTPUT MOTOR CURRENT B10 B11 4 20 mA SUPPLY VOLTAGE 18 30 VA...

Page 6: ...Interface AP ASCII protocol as standard Connection Terminals B1 B2 B3 3 pole spring clamp connector terminals Analog Output Motor Current Monitoring Interface 4 20 mA max burden 200 Connection Termin...

Page 7: ...h the serial communications network if connected on the network side of the Remote Operator SOFT STARTER START STOP DATA PROG RESET START RUN TRIP RS485 AMPS TEMP CODE Stop Pushbutton Start Pushbutton...

Page 8: ...and 1 11 instead of motor temperature N B When using the Remote Operator with MCD 500 models MCD5 0023B MCD5 0068B the motor current and analog output must be normalised using Pars 6 and 9 Programmab...

Page 9: ...rameter Parameter 7 This is set to give a 4 mA output signal when the motor current is zero The 4 20 mA analog output has an accuracy of 10 It is not designed for process signal control use and should...

Page 10: ...mote Operator start stop quick stop function enabled Network start stop quick stop function disabled 2 Remote Operator start stop quick stop function disabled Network start stop quick stop function en...

Page 11: ...5 LED flashing The Remote Operator has detected a loss of communication on the RS485 link to the soft starter Verify and solve the cause for loss of communication If communication is restored before t...

Reviews: