background image

 

MCC 101 - Sine Wave Filter

 

Installation guidelines 

Installationsanweisungen 

 

Mounting / Montage 

–  Mount the filter vertically with the output (motor side) at the bottom 
–  Do not mount the filter close to other heating elements or heat sensitive material (such as wood) 
–  Filter can be side-mounted with the frequency converter. There is no requirement for spacing 

between the filter and frequency converter. 

 
– 

Filter senkrecht und mit dem Filteranschluss (Motorseite) nach unten befestigen 

–  Nicht in der Nähe von temperaturempfindlichen Elementen montieren. 

– 

Das Filter kann direkt neben dem Frequenzumrichter montiert werden. Es gibt keine 
Einschränkungen bezüglich des Mindestabstands zwischen Frequenzumrichter und Filter. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Earthing / Erdung 

The filter must be earthed before switching the power on (high leakage currents). 
Common mode interferences are kept small by ensuring that the current return path to the VLT® has 
the lowest possible impedance. 
–  Choose the best earthing possibility (e.g. cabinet mounting panel) 
–  Use the enclosed (in accessory bag) protective earth terminal to ensure the best possible earthing 
–  Remove any paint present to ensure good electrical contact 
–  Ensure that the filter and VLT® make solid electrical contact (high frequency earthing) 
 

Die Gleichtaktstörungen werden klein gehalten, indem man dafür sorgt, dass die Ströme möglichst 
niederimpedant zur Quelle zurückgeführt werden. 
–  Beste Erdungsmöglichkeit wählen (z.B. Montageplatte des Schaltschrankes) 

– 

Grossflächiges Kontaktieren von Filter und Frequenzumrichter (HF-Erdung) 

– 

Benutzen Sie die in mitgelieferte PE Klemme für eine optimale Erdung.  

– 

Entfernen vorhandener Farbe, so dass eine gute Kontaktierung gewährleistet ist 

– 

Das Filter ist unbedingt vor dem Einschalten zu erden (erhöhter Ableitstrom) 

 

Screening / Schirmung 

It is recommended to use screened cables to reduce the radiation of electromagnetic noise into the 
environment and prevent malfunctions in the installation. 
–  Cable between the VLT® output (U, V, W) and filter input (U1, V1, W1) to be screened or twisted. 
–  Use preferably screened cables between the filter output (U2, V2, W2) and the motor. When 

unscreened cables are employed it should be ensured that the installation minimizes the possibility 
of cross-couplings with other cables carrying sensitive signals. This can be achieved by measures 
such as cable segregation and mounting in earthed cable trays. 

–  The screen on screened cables must be solidly connected at both ends to the housings (e.g. 

housing of filter and motor). 

–  All screen connections must exhibit the smallest possible impedance, i.e. solid, large area 

connections, both ends of shielded cable. 

–  For maximum cable length consult the Design Guide of the VLT® in question 
 

Es ist empfehlenswert auch bei Einsatz eines Ausgangsfilters das Motorkabel geschirmt auszuführen 
um die Störabstrahlung an die Umgebung zu begrenzen und Anlagenstörungen vorzubeugen. 
–  Kabel zwischen Umrichterausgang (U, V, W) und Filtereingang (U1, V1, W1) möglichst geschirmt 

oder verdrillt ausführen. 

– 

Es ist vorzugsweise zwischen Filterausgang (U2, V2, W2) und Motor geschirmtes Kabel zu 
verwenden. Sollte dies nicht vorgesehen sein, muss sichergestellt werden, dass die Installation 
die Warscheinlichkeit von gegenseitigen Einkopplungen z.B. mit Signalkabeln ausschließt. Dies 
kann u.a. durch eine gute räumliche Trennung und Verlegung der Kabel in geerdeten 
Metallkanälen erreicht werden. 

–  Bei geschirmten Leitungen muss der Schirm beidseitig grossflächig mit den Gehäusen verbunden 

werden (z.B. Filter- und Motorgehäuse). 

– 

Alle Schirmverbindungen möglichst niederimpedant, sprich grossflächig auslegen (z.B. Schirm 
unter den Befestigungsbolzen des Filters montieren

). 

–  Die maximale Kabellänge ist dem Projektierungshandbuch des jeweiligen VLT® zu entnehmen. 
 
 

Block diagram / Anschlussschema 

 

VL

T fr

eq

uen

cy 

co

nv

er

ter

Sine wave filter

MC

O

 

 

 

 

 

 

 

 

 

 

MI.90.N1.5B - VLT

®

 is a registered Danfoss trademark 

Shielded or 

twisted cable 

Screened 

cable 

Reviews: