4 | AN307529759541en-000101

© Danfoss | DCS (vt) | 2019.06

Tone select

1. 

Tone

Tone 

select

Tone description

Application

mA @

12VDC

dB(A) 

@1m,

90°, 

12VDC

mA @

24VDC

dB(A) 

@1m,

90°, 

24VDC

0

111111

Rising and falling 150 to 1000 to 150 Hz 10 s - 40 s - 10 s

Highest

27

93

35

97

1

011111

Alternating

800 & 970 Hz

2 Hz (250 ms - 250 ms)

BS Fire

20

93,5

30

98

2

101111

Rising

800 & 970 Hz

7 Hz (7/s)

BS Fire

20

93

29

97

3

001111

Rising

800 & 970 Hz

1 Hz (1/s)

BS Fire

20

94

30

97

4

110111

Constant tone

2850 Hz

Continuous

18

88

23

95

5

010111

Rising

2400 to 2850 Hz

7 Hz (7/s)

18

87

23

95

6

100111

Rising

2400 to 2850 Hz

1 Hz (1/s)

17

87

23

96

7

000111

Rising

300 to 1200 Hz

3s rising, 0.5s silence, then repeat

Netherlands Fire (NEN 2575)

20

94

23

98

8

111011

Falling

1200 to 500 Hz

1 Hz

German Fire (DIN 33 404)

21

93

31

98

9

011011

Alternating

2400 & 2850 Hz

2 Hz (250 ms - 250 ms)

18

87

24

95

10 101011

Interrupted

970 Hz

0.5 Hz (1s ON/ 1s OFF)

PFEER alert

17

92

20

97

11 001011

Alternating

800 & 970 Hz

1 Hz (500 ms - 500 ms)

BS Fire

20

93

30

97

12 110011

Interrupted

2850 Hz

0.5 Hz (1s ON/ 1s OFF)

17

88

21

96

13 010011

Interrupted

970 Hz

0.8 Hz (250 ms ON/1s OFF)

17

92

21

97

14 100011

Constant tone

970 Hz

Continuous

PFEER toxic gas

20

92

28

97

15 000011

Alternating

554 & 440 Hz

100 ms - 400 ms

French Fire (NFS32-001)

22

91

35

96

16 111101

Interrupted

660 Hz

3.3 Hz (150 ms ON/150 ms OFF)

Swedish (Air Raid)

18

91

26

96

17 011101

Interrupted

660 Hz

0.28 Hz (1.8 s ON/1.8 s OFF)

Swedish (local warning)

18

91

23

96

18 101101

Interrupted

660 Hz

0.05 Hz (6.5 s ON/13 s OFF)

Swedish (Pre-mess)

18

91

26

96

19 001101

Constant tone

660 Hz

Continuous

Swedish (All  Clear)

20

91

31

96

20 110101

Alternating

554 & 440 Hz

0.5 Hz (1s ON/ 1s OFF)

Swedish (Turn out)

22

91

35

96

21 010101

Interrupted

660 Hz

1 Hz (500 ms - 500 ms)

Swedish common

20

91

21

96

22 100101

Interrupted

2850 Hz

4 Hz (150 ms ON/100 ms OFF)

Pelican crossing

18

88

22

95

23 000101

Ansteigend

800 to 970 Hz

50 Hz

BS Fire

21

90

30

96

24 111001

Ansteigend

2400 & 2850 Hz

50 Hz

20

85

25

93

25 011001

Interrupted

970 Hz

3 x 500 ms Pulse followed by 1.5 s 

silence, then repeat

ISO 8201

19

92

23

97

26 101001

Interrupted

2850 Hz

3 x 500ms Pulse followed by 1.5 s 

silence, then repeat

ISO 8201

19

88

23

95

27 001001

Constant tone

4000 Hz

Continuous

ISO 8201

19

90

23

95

28 110001

Alternating

800 & 970 Hz

2 Hz (250 ms - 250 ms)

BS Fire

22

93

30

97

29 010001

Alternating

990 & 650 Hz

2 Hz (250 ms - 250 ms)

BS Fire

23

92

35

97

30 100001

Alternating

510 & 610 Hz

2 Hz (250 ms - 250 ms)

BS Fire

23

91

35

96

31 000001

Rising

300 to 1200 Hz

1 Hz

22

93

34

97

32 111110

Constant tone

4000 Hz

Continuous

BS Fire

20

91

25

96

33 011110

Constant tone

990 Hz

Continuous

21

92

30

97

34 101110

Interrupted

990 Hz

1 Hz (500 ms ON/500 ms OFF)

19

92

21

97

35 001110

Constant tone

510 Hz

Continuous

23

91

35

96

36 110110

Interrupted

510 Hz

1 Hz (500 ms ON/500 ms OFF)

20

91

22

96

37 010110

Constant tone

850 Hz

Continuous

21

89

30

96

38 100110

Constant tone

1650 Hz

Continuous

20

86

24

94

PFEER    

Prevention of Fire Explosion and Emergency Response

BS  

 

British Standard

DIN  

 

Deutsche Industrie Norm

ISO  

 

International Organisation of Standardization

Summary of Contents for 080Z2819

Page 1: ...Strobe and Horn unit may be connected to the DGS Note A single 470 ohm resistor is supplied with the product and must be used when the S H is powered from the DGS and the DGS is powered by AC power see page 3 Alarm Sounder Current consumption 9 35 mA Siren 4 6 mA Flash Operating volltage 9 28V DC IP rating IP 65 Operating temp 20 70 C 4 0 F 158 F Sound output 67 100 dB A 98 dB A at DIN Tone Potent...

Page 2: ... 1 2 3 x6 x5 Rel 3 Rel 1 x4 4 3 2 1 not used JP3 JP2 JP1 x3 Ackn Test button Sensor 1 Sensor 2 Tool x9 x2 x8 B L JP4 Danfoss 80Z815 10 open 19200 Baud closed 38400 Baud B Modbus A 24V DC 1 2 3 4 5 6 GND A Strobe Horn on Rel 1 B Strobe on Rel 1 Horn on Rel 3 failure D Botton digital input S H B B A D D Note A Strobe and Horn on Rel 1 D Button digital input B Strobe on Rel 1 Horn on Rel 3 failure ...

Page 3: ... x6 x5 Rel 3 Rel 1 x4 4 3 2 1 not used JP3 JP2 JP1 x3 Ackn Test button Sensor 1 Sensor 2 Tool x9 x2 x8 B L JP4 Danfoss 80Z816 10 open 19200 Baud closed 38400 Baud B Modbus A 24V AC 1 2 3 4 5 6 GND A Strobe Horn on Rel 1 B Strobe on Rel 1 Horn on Rel 3 failure D Botton digital input S H B B A D D R B R R 470 Ω Note A Strobe and Horn on Rel 1 D Button digital input B Strobe on Rel 1 Horn on Rel 3 fa...

Page 4: ... 23 96 18 101101 Interrupted 660 Hz 0 05 Hz 6 5 s ON 13 s OFF Swedish Pre mess 18 91 26 96 19 001101 Constant tone 660 Hz Continuous Swedish All Clear 20 91 31 96 20 110101 Alternating 554 440 Hz 0 5 Hz 1s ON 1s OFF Swedish Turn out 22 91 35 96 21 010101 Interrupted 660 Hz 1 Hz 500 ms 500 ms Swedish common 20 91 21 96 22 100101 Interrupted 2850 Hz 4 Hz 150 ms ON 100 ms OFF Pelican crossing 18 88 2...