6. Minimum distances from combustible or heat sensitive materials:
The technical data sheet and the EN plate on the stove contain the data referring to the stove that might differ from these
standard regulations.
In case of combustible floors, being sensitive to a rise in temperature, non-combustible floor protector must be used. This
floor protector must reach 30 cm beyond the front (front of combustion chamber), 15 cm beyond the side of the Stove. The
floor protector can be made of fire proof material at least 12mm thick, 12mm glass or slate plates are acceptable..
The given minimum safety distances from combustible or heat sensitive materials have to be kept by all means at the back,
the front and sideways.
Distance to
combustible rear
Distance to
combustibles side
Suitable for 12mm floor
plate
Distance to soft furnishings
Mandø
200mm
300mm
yes
1000mm
Rømø
200mm
300mm
yes
1000mm
Samsø
200mm
300mm
yes
1000mm
Læsø
250mm
600mm
yes
1000mm
More information about safety distances from the connecting pipe can be found at the description of connecting.
7. Preparing the appliance for connection:
Height
mm
Width
mm
Depth
mm
Outlet
mm
Distance from rear centre of
top outlet mm
Height to centre of rear
outlet mm
Mandø
814
510
479
150
194
690
Rømø
1001
510
479
150
194
877
Samsø
985
430
361
150
148
860
Læsø
927
437
330
150
142
n/a
Choose top or rear flue connection. (Læsø model has top flue exit only.)
The Flue diameter of flue outlet is 150 mm.
All DANBURN appliances are sold setup as a top flue outlet. We recommend this connection mode because of combustion
technological reasons. In case you would like to connect the stove at the back (technical data sheet contains the connection
height), remove the flue outlet from the top and the closing lid from the back. Put the flue at the back, and close the top
outlet with the closing lid. Carefully ensure cover plate and collar are securely refitted using air tight rope seals.
Readjusting the flue outlet from the back to the top:
Remove the flue outlet from the back and the closing lid from the top. Put the flue outlet on the top and the closing lid on the
rear outlet.
Cover the rear outlet with a heat protecting plate as well.
Carefully insulate the outlets.
In case of top connection:
The height of connection can be chosen without any restriction but it cannot exceed 1 meter above the upper edge of the
stove. It is recommended that cleaning hatches are fitted on flue elbows to improve ease of cleaning.
In case of stoves with a capacity of 6kW the minimum length of the vertical connecting pipe is 50 cm.