Configuration & control of the AC SuperDrive
6.4.1.7 P
ARAMETER CONTROLLED RAMP
In the Parameter Controlled Ramp mode, the ramp is controlled from the PDO but the actual
ramp values are given by parameters (accessible via SDOs). The PDO has exactly the same
contents as for No Ramp Mode, except that five extra bits are used in the Command Word (
Bit
Description
1-2
Speed Neutral Brake Ramp Parameter Set (0-3). See object indexes 2104h - 2105h.
11-12
Speed Ramp Parameter Set (0-3). See object indexes 2100h - 2103h.
13
Foot Brake Active, 1 = True.
Table 13. Parameter Controlled Ramp - Command Word.
In order to improve the ramp functionality it is also possible to include the parameters 2000h:7
and 2000:8 shown in
in the PDO. The receive PDO then looks as in Table 14.
1
2
3
4
5
6
7
8
Command Word
Command Speed
Acceleration
Reduction
Factor
Max Speed
Reduction
Factor
Optional
Table 14. PDO controlled ramp - Receive PDO contents.
Index
Sub-
Index
Name
Description
2000h 7
Acceleration
Reduction Factor
UsedAcceleration =
Acceleration * AccelerationReductionFactor / 128
AccelerationReductionFactor = 128 means no reduction.
2000h 8
Max
Speed
Reduction Factor
Reduction of parameter Max Speed that is used during
Reverse Brake.
UsedMaxSpeed=
MaxSpeedInRpm*(MaxSpeedReductio1)/256
MaxSpeedReductionFactor = 255 means no reduction.
2120h
1
Max Speed
Used during Reverse Brake.
Table 15. Parameter Controlled Ramp – Parameters.
User's Guide 1.0
Item No.
89Y05120A
51
Summary of Contents for SuperDrive ACS24 Series
Page 12: ......
Page 34: ......
Page 38: ......
Page 79: ...26 04 2005 Troubleshooting guide User s Guide 1 0 Item No 89Y05120A 79...
Page 81: ...26 04 2005 Troubleshooting guide User s Guide 1 0 Item No 89Y05120A 81...
Page 82: ...Troubleshooting guide 26 04 2005 Item No 89Y05120A User s Guide 1 0 82...
Page 92: ......