7
PARAMETERS
CODE
DESCRIPTION
SET
VALUE
PRESSURE
CONTROL
0
* ( 0 = TRANSDUCER, 1 = PRESURE
SWITCH
)
TOP RANGE PRESSURE TRANSDUCER
15 Bar
HIGH PRESSURE ALARM
8,8 – 11 – 14,3 Bar
STOP
PRESSURE
7,5 – 10 – 13 Bar
START
PRESSURE
6,5 – 9 – 12 Bar
OFFSET PRESSURE TRANSDUCER
0
MAX.
TEMPERATURE
SET
110
°
C
HIGH TEMPERATURE ALARM SET
105
°
C
FOREWARNING HIGH TEMPERATURE SET
100
°
C
LOW
TEMPERATURE
SET
0
°
C
TEMPERATURE SENSOR OFFSET
0
°
C
STAR TIMER
5 sec.
STAR/DELTA SWITCHING TIMER
50 msec.
LOAD
DELAY
TIMER
2
sec.
UNLOAD
STOP
TIMER
2
min.
UNLOAD STOP TIMER VARIABLE
0
STOP TIMER
30 sec.
AIR FILTER CHANGE TIME
2000 Hours
OIL
FILTER
CHANGE
TIME
2000
Hours
SEPARATOR
CHANGE
TIME
4000
Hours
OIL
CHANGE
TIME
2000
Hours
CHECK
KOMPRESOR
2000
Hours
STARTS/ HOURS ALLOWED TO THE MOTOR
6
LOW
VOLTAGE
ALARM 1
RL5 SET
0
FAN ON (RL5)
85
°
C
DELTA T FAN OFF (RL5)
10
°
C
ATTENTION : P18- P22 COUNTDOWN IDENTIFY THE MOTOR RUNNING TIME, WHEN THE COUNTDOWN IS ELAPSED THE TIMER
WILL GO ON AS NEGATIVE COUNTING.