DGM01
– SERVER GATEWAY – FW 3.0
Gateway ETHERNET-MODBUS-DMX512A-DALI
Function manual
Made in Italy
Rev. 2016-09-19
pag. 2/22
Reference Standards
EN 55022:2010
Information technology equipment - Radio disturbance characteristics - Limits and methods of measurement
EN 55024:2010
Information technology equipment - Immunity characteristics - Limits and methods of measurement
EN 60950-1:2006 + A1:2010 +
A2:2013 + A11:2009 + A12: 2011
Information technology equipment - Safety
IEC/EN 62386-101
Digital addressable lighting interface - Part 101: General requirements - System
IEC/EN 62386-102
Digital addressable lighting interface - Part 102: General requirements - Control gear
IEC/EN 62386-207
Digital addressable lighting interface - Part 207: Particular requirements for control gear - LED
modules (device type 6)
ANSI E 1.3
Entertainment Technology - Lighting Control Systems - 0 to 10V Analog Control Specification
ANSI E1.11
Entertainment Technology - USITT DMX512-A - Asynchronous Serial Digital Data Transmission
Standard for Controlling Lighting Equipment and Accessories
ANSI E1.20
Entertainment Technology-RDM-Remote Device Management over USITT DMX512 Networks
-
MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1b
Technical Notes
Installation:
• Installation and maintenance must be performed only by qualified personnel in compliance with current regulations.
• The product must be installed inside an electrical panel protected against overvoltages.
• The product must be installed in a vertical or horizontal position with the cover / label upwards or vertically; other positions are not permitted.
It is not permitted the bottom-up position (with the lower face plate / label).
• Keep separate the 230V circuits (LV) and not SELV circuits from safety extra low voltage (SELV) and all connections for this product. It's
absolutely forbidden to connect, for any reason, directly or indirectly, the 230V mains voltage to the bus or to other parts of the circuit.
Power Supply:
• For power supply use only SELV power supplies with limited current and short circuit protection, and of appropriately sized power. In case of
power supplies provided with an earth terminal, ALL protective earthing points (PE = Protection Earth) must be connected to a valid
protection earth.
• The connection cables between the power source and the product must be sized properly and should be isolated from any wiring or live
parts not SELV. Use double insulated cables.
Commands:
• The length of the connecting cables between the local controls (push button, 0-10V, 1-10V, potentiometer, or other) and the product must be
less than 10m; the cables must be sized properly and should be isolated from any wiring or live parts not SELV. Use double insulation
shielded and twisted cables.
• The length and type of the bus cables (DMX512, Modbus, DALI, Ethernet or other) must comply with the specifications defined by the
respective protocols and the respective regulations; They should be isolated from any wiring or live parts not SELV. Use shielded cables and
twisted double insulation.
• All devices and related control signals to the bus (DMX512, Modbus, DALI, Ethernet or other) and to the local controls (push button, 0-10V,
1-10V, potentiometer, or other) must be SELV (connected devices must be SELV or otherwise provide a SELV signal).