Page
43
of 77
SK2019 FCSD(H)-V/P-ECM-001
Control Specifications: Complete Control PCB
–
EC-S1 Control
Abbreviations
Ts = Setting temperature
AUX1 = Hot water free contact
Tr = Room air temperature
AUX2 = Chilled water free contact
Ti1 = Chilled water coil temperature
MTV1 = Chilled water valve
Ti2 = Hot water coil temperature
MTV2 = Hot water valve
I/O Port Definitions
I/O
Code
2-Pipe
4-Pipe
Analogue
Input
Return
air sensor
AI1
Return air temperature (Tr)
2-pipe coil circuit sensor
AI2
Chilled / hot water coil circuit
(Ti1)
Chilled water coil circuit
(Ti1)
Hot water sensor
AI3
N/A
Hot water coil circuit (Ti2)
Input
LED display / IR receiver
X-DIS 1
Digital communication port to LED display / IR receiver board.
Wired wall pad
TTL1
Digital communication port to wired wall-pad board.
Digital input
Occupancy contact
ON/OFF
Window contacts: for remote ON/OFF (when DIPB SW1=1).
Economy mode contacts: for remote activation of economy mode (when DIPB
SW1=0).
Float switch
Float
Voltage-free (NC)
Electrical heater safety
switch
EH
Voltage-free (NC). The contact is closed before the EH is turned on.
Power input
Phase
L1
Power supply to the PCB and all the loads connected to the voltage outputs.
Neutral
N1
Power supply to the PCB and all the loads connected to the voltage outputs.
Earth
PE1
Power supply to the PCB and all the loads connected to the voltage outputs.
Voltage
output
Fan 1
CN4
Fan 1 driver and motor connection port.
Fan2
CN5
Fan 2 driver and motor connection port.
Valve1
MTV1
2-pipe coil circuit valve output –
chilled / hot water valve.
Voltage output (L)
4-pipe coil circuit valve output –
chilled water valve.
Voltage output (L)
Valve2
MTV2
Reserved
4-pipe coil circuit valve output – hot
water valve.
Voltage output (L)
Water pump
WP
Voltage output (L)
Power supply to condensate pump.
Voltage of electrical
heater (Live)
L-EH
Voltage output (L), maximum 30A.
[See wiring diagram, cross check with supplier.]
Stepping motor
CN1-2
Power supply to louver stepping motors
Voltage output (L)
Output
Auxiliary contact 2
AUX2
Cooling mode signal relay (NO). Voltage free contact.
Auxiliary contact 1
AUX1
Heating mode signal switch (NO). Voltage free contact.
Serial BUS port
CN3
Master-slave network serial connection OR
MODBUS / local PC host network serial connection.
24VAC power input
DA1
24VAC external power supply (modulating valve applications only).
Modulating valve output
1
DA2
Connection to DC modulating valve
on 2-pipe coil circuit
- chilled / hot water.
Connection to DC modulating valve
on 4-pipe coil circuit
- chilled water.
Modulating valve output
2
DA3
N/A
Connection to DC modulating valve
on 4-pipe coil circuit
- hot water.
Summary of Contents for FDLA-09
Page 1: ...SK2018 GLOBAL FDLA V P AC 001 FDLA V P AC MOTOR...
Page 27: ...Page 26 of 51 SK2018 GLOBAL FDLA V P AC 001 Configuration Settings...
Page 53: ...FDHD V P AC MOTOR...
Page 69: ...B 1 4 4 Electrical connections T Configuration standard version...
Page 74: ...Wiring Diagram D 2 SK NCPDWH 001b S Configuration Full Control PCB...
Page 76: ...Configuration Settings D 3...
Page 111: ......
Page 112: ...SK2019 FCSD H V P ECM 001 FCSD H V P ECM MOTOR...
Page 190: ...SK2019 FCSD H V P ECM 001...
Page 191: ...Page 1 of 59 SK2015 FMCD V EC 001 FMCD ECM MOTOR...
Page 210: ...Page 20 of 59 SK2015 SWC V EC 001 D 1 3 Wiring Diagram SK NCSWC 001...
Page 233: ...Page 43 of 59 SK2015 SWC V EC 001 D 4 2 Wiring diagram SK NCSWC 002...
Page 248: ...Page 58 of 59 SK2015 SWC V EC 001 Troubleshooting Guide E 4...
Page 249: ...Page 59 of 59 SK2015 SWC V EC 001...
Page 250: ...FSTD C V P ECM MOTOR...
Page 256: ...Page 7 of 73 SK2015 FSTDC V P ECM 001 A 2 Unit Appearance FSTDC VAR FSTDC HAR FSTD...