52
BIT15
BIT14
BIT13
BIT12 Reserved
BIT11 EUV 1: free electricity; 0: judge by SG's signal
BIT10 SG 1: normal electricity; 0: high price electr
icity (judge when EUV is 0)
BIT9 Anti-freezing operation for water tank
BIT8 Solar energy signal input
BIT7 Cooling mode set by room thermostat
BIT6 Heating mode set by room thermostat
BIT5 Outdoor unit test mode mark
BIT4 Remote On/Off (1: d8)
BIT3 Oil return
BIT2 Anti-freezing
BIT1 Defrosting
BIT0 Reserved
BIT15 DEFROST
BIT14 Auxiliary heat source
BIT13 RUN
BIT12 ALARM
BIT11 Solar water pump
BIT10 HEAT4
BIT9 SV3
BIT8 Mixed water pump P_c
BIT7 Water return water P_d
BIT6 External water pump P_o
BIT5 SV2
BIT4 SV1
BIT3 Water pump PUMP_I
BIT2 Electric heater TBH
BIT1 Electric heater IBH2
BIT0 Electric heater IBH1
130(PLC: 40131)
Software version
131(PLC: 40132)
Wired controller version No.
128(PLC: 40129)
Status bit 1
129(PLC: 40130)
Load output
1~99 is the software version of hydronic module
1~99 is the wired controller's version number.
Request to send operation parameter, 1:
request; 0: not request
Request to send software version, 1:
request; 0: not request
Request to send SN code, 1: request; 0: not
request
Summary of Contents for AIWD URBAN II Series
Page 23: ...20 2...
Page 24: ...21 15...
Page 33: ...30 6 2 3 Add Home Appliances 1 Add your device following the guidance...
Page 34: ...31 2 Operate the wired controller according to APP prompts...
Page 35: ...32 3 Wait for the home appliance to connect and click Sure...
Page 43: ...40 7 3 1 Structure size figure 19mm 84mm 44mm 46mm 60mm 120mm 20mm 120mm Figure A...
Page 64: ...Eurofred S A Marqu s de Sentmenat 97 08029 Barcelona www eurofred es...