Dairyland SWX-100-PED Installation And Operating Instructions Manual Download Page 2

REQUIRED TOOLS

Required user-furnished installation tools include: (a) a ratchet 

wrench with ½” and ¾” sockets, (b) a ½” and ¾” box end 

wrench, (c) a battery operated drill with a 9/16” drill bit, (d) a 

center-punch, (e) a suitable grounding jumper and electrically 

insulated gloves as mentioned above, (f) electrical insulating 

tape, (g) a multimeter to measure ac voltage, (h) and a padlock 

that fits a 7/16” hole in the isolation switch latch. 

INSTALLATION PROCEDURE FOR ANY PEDESTAL  

OR DECOUPLER MODEL

Note: The photos used in the installation steps will show the switch being 

connected to a SSD in a now discontinued MTP-42 pedestal. All steps remain 

the same regardless of mounting pedestal model number. 

1. Two 9/16” holes are required in the pedestal cover to mount 

the isolation switch. It is very important to install this switch to 

the one correct face of the cover for each pedestal model. 

2. The correct cover face on the standard Dairyland pedestal 

(MTP-36) is the face on which the head of the two pedestal cov-

er latch pins are visible near the bottom end of the cover. Two 

9/16” holes in the cover are required for mounting the isolation 

switch. Use the “Hole Location Template and Drilling Instruc-

tions” furnished with each isolation switch to drill these holes 

and then remove the pedestal cover and lay it flat it so the two 

holes are on the right or left side. Hole location is very important. 

See Appendix for template information.

3. Open the isolation switch cover. If ON appears above the 

right corner of the pull-out switch, then pull out by the handle, 

rotate 180° and plug back in so OFF appears below the left cor-

ner of the pull-out switch and close the cover.  If OFF appeared 

when the cover was first opened, then leave as-is and close the 

cover.

4. Remove the two brass nuts and stainless washer from each 

stud projecting from the bottom of the enclosure, but leave the 

two rubber gaskets on each stud.

 

5. Insert the two ½” studs of the switch through the two holes 

drilled in the pedestal cover so the switch is upright (i.e., so the 

nameplate is readable when the cover is later reinstalled on the 

base). It may be necessary to slightly force the two studs closer 

together or further apart to insert through the two holes if they 

were not drilled precisely per the template hole location marks.

6. On the inside of the pedestal cover, install on each stud one 

stainless steel washer and one hex brass nut threaded all the 

way on the stud hand tight.  Using a ¾” box wrench or ratchet 

wrench, tighten each brass nut until the flange of the enclosure 

is snug against the outside wall of the pedestal cover to assure 

a good seal, but do not over tighten.  Stop tightening when the 

force required to turn the nut rather abruptly increases.

Dairyland Electrical Industries  •  P.O. Box 187 Stoughton, WI 53589  •  608-877-9900  •  www.dairyland.com  •  [email protected]

Required Tools

Grounding Cables: BCL-1/0 (Left) BCL-2 

(Right) 

MTP-36 Cover Face

Switch On

Switch Off

Note: When the installation is to a PCR rated 10kA or higher, the BCL-1/0 grounding 

cable is suggested and for any SSD, the BCL-2 is suggested.