70
WGZ030D through WGZ200D
OMM 1130
-
2
TEST
The test screens are only available when the unit is in TEST mode. Using these screens, any digital
output can be controlled manually.
R22, R407 C
R410 A
TEST UNIT (1)
TEST UNIT (1)
Alarm Signal =OFF
Alarm Signal =OFF
Evap Pump 1 = OFF
Evap Pump 1 = OFF
Evap Pump 2 = OFF
# of Com pressors = 4
# of Com pressors = 6
TEST UNIT (2)
TEST UNIT (1)
Liq Line Sol #1= OFF
Liq Line Sol #1= OFF
CompressorHG1 = OFF
Compressor HG1 = OFF
1= OFF 3= OFF
1= OFF 3= OFF 5= OFF
# of Com pressors = 4
# of Com press ors = 6
TEST UNIT (3)
TEST UNIT (3)
Liq Line Sol #2=OFF
Liq Line Sol #2=OFF
Compressor HG2 = OFF
Compressor HG2 = OFF
2= OFF 4= OFF
2= OFF 4= OFF 6= OFF
Wat er Co ol ed = O N
Wat er Co ol ed = O F F
TEST UNIT (4)
TEST UNIT (4)
Cond Pump 1 = OFF
Fan 1=OFF Fan 3=OFF
Cond Pump 2 = OFF
Fan 5/7=OFF
TwrFan1=OFF Fan2=OFF
Fan 9=OFF
Wat er Co ol ed = O N
Wat er Co ol ed = O F F
TEST UNIT (5)
TEST UNIT (5)
Twr Bypass= XXX.X %
Fan 2=OFF Fan 4=OFF
Twr VFD= XXX.X %
Fan 6/8=OFF
Fan 10=OFF
TEST UNIT (6)
EXV Cir 1= XXX.X %
EXV Cir 2= XXX.X %
Editing Review
Editing shall be accomplished by pressing the ENTER key until the desired field is selected. This field
shall be indicated by a blinking cursor under it. The arrow keys shall then operate as defined below.
CANCEL (Right) Reset the current field to the value it had when editing began.
DEFAULT (Left)
Set value to original factory setting.
INCREMENT (Up) Increase the value or select the next item in a list.
DECREMENT (Down) Decrease the value or select the previous item in a list.
During edit mode, the display shall show a two-character wide menu pane on the right as shown below.