Operation mode
1.
Used to display the current operation
●
mode: Cool, Heat, Vent, Fan, Dry or Auto.
Fan Speed
2.
Used to display the fan speed that is set for the indoor unit.
●
The fan speed will not be displayed if the connected model does
●
not have fan speed control functionality.
Setpoint display
3.
Used to display the setpoint for the indoor unit.
●
Use the Celsius/Fahrenheit item in the main menu to select the
●
temperature unit (Celsius or Fahrenheit).
Stand by for Defrost/Hot start
4.
“
STANDBY
”
(See page 12.)
If ventilation icon is displayed in this
fi
eld:
Indicates that an energy recovery ventilator is connected.
●
For details, refer to the Operation Manual of the ERV.
Message
5.
The following messages may be displayed.
“This function is not available”
Displayed for a few seconds when an operation button is pressed
●
and the indoor unit does not provide the corresponding function.
In a remote control group, the message will not appear if at least
●
one of the indoor units provides the corresponding function.
“Error: Push Menu button”
“Warning: Push Menu button”
Displayed if an error or warning is detected
●
(see page 32)
.
“Time to clean
fi
lter”
“Time to clean element”
“Time to clean
fi
lter & element”
Displayed as a reminder when it is time to clean the
fi
lter or
●
element
(see page 31).
Ventilation
6.
Displayed when a energy recovery ventilator is connected.
●
Ventilation Mode icon.“
●
AUTO
ERV
ERV
BYPASS
”
These icons indicate the current ventilation mode (ERV only)
(AUTO, ERV, BYPASS).
Air Purify ICON “
●
AIR
PURIFY
”
This icon indicates that the air purifying unit (option) in operation.
7. display
(See page 16.)
Displayed when the key lock is set.
●
8. display
(See page 21.)
Displayed if the Schedule or Off timer is enabled.
●
Under Centralized control “
9.
CENTRAL
CONTROL
”
Displayed if the system is under the management of a multi zone
●
controller (option) and the operation of the system through the
remote controller is limited.
Changeover controlled by the master indoor unit
10.
“
MASTER
CONTROLLED
”
Displayed when another indoor unit on the system has the
●
authority to change the operation mode between cool and heat.
Setback “
11.
SETBACK
”
(See page 13.)
The setback icon
fl
ashes when the unit is turned on under the
●
setback control.
Air Flow Direction “
12.
”
Displayed when the air
fl
ow direction and swing are set
●
(see page
19)
.
If the connected indoor unit model does not include oscillating
●
louvers this item will not be displayed.
Current Day/Time (12/24 hour time display)
13.
Displayed if the clock is set
●
(see page 29)
.
If the clock is not set, “ -- : -- ” will be displayed.
●
12 hour time format is displayed by default.
●
Select 12/24 hour time display option in the main menu under
●
“Clock & Calendar”.
Detailed selection
14.
Displayed if the detailed display item is selected
●
(see page 28)
.
Detailed items are not selected by default.
●
15. display
Displayed when the clock needs to be set.
●
The schedule function will not work unless the clock is set.
●