Standby Control
Part 4 Functions and Control
59
3. Standby Control
3.1 Restart Standby
Used to forcedly stop the compressor for a period of 5 minutes, in order to prevent the frequent
ON/OFF of the compressor and equalize the pressure within the refrigerant system.
In addition, the outdoor fan carry out the residual operation for a while to accelerate pressure
equalizing and to suppress melting of the refrigerant to the evaporator.