Symptom-based Troubleshooting
SiME341909EA
140
Part 6 Service Diagnosis
2.1 With Optional Infrared Presence/Floor Sensor
Error diagnosis of "Louver operation different from setting"
Problem
Measure
1 Louver operation different from setting
Refer to the flowchart below.
2 Individual airflow direction setting different from the actual
airflow direction
Check the "Louver operation different from setting" error
diagnosis.
3 While not operating, the louver does not close completely.
Turn off the circuit breaker and then turn it on again.
4
The remote controller menu does not display energy saving
operating mode for when people are not present.
Please check
Infrared presence floor sensor error
(CE)
in troubleshooting.
The remote controller menu does not display the stop function
for when people are not present.
The remote controller menu does not display the automatic
draft prevention function.
5 The menu does not display the eco-friendly display function.
No defect.
Set the clock.
6
During cooling and dry operation, the louver automatically
switches from horizontal (P0) to one-level downward (P1).
No defect.
When relative ambient humidity is higher, automatic louver
control will be activated.
7
Although people are not present, the infrared presence sensor
detects human presence.
Check if there are any objects that generate temperature
change when moving.
For example:
· An electric heater with swing function
· Doors, curtains, blind switches
· Output of paper from a fax machine or a printer
· Turning on/off of incandescent lights
· Moving objects
8
Although people are present, the infrared presence sensor fails
to determine their presence.
Check for the following conditions.
· Lack of movement
· Facing away from the sensor
· Little skin exposed
· Slight movement in a place far from the sensor
9
Large difference between floor temperature and actual
temperature
Check for the following conditions.
· Sensor detection zone affected by solar radiation
· High or low temperature objects in the sensor detection
zone
· Large difference between floor temperature and
temperature of the living space
· Sensors installed near walls may be affected by wall
temperature.
Normal
Reset (Cancel)
individual airflow.
Is the individual
airflow set?
Is the
airflow direction set to
automatic?
Is the
wire harness
broken?
YES
YES
NO
NO
NO
NO
NO
Replace the step
motor. (Motor failure)
YES
Replace the wire
harness.
YES
Is the connection
of the step motor
connector normal?
Is the
automatic draft prevention
function "enabled"?
YES
Normal
Automatic draft
prevention function
switches flap to
horizontal position
when human
presence is detected.
Connect to the
connector
correctly before
action verification.
Summary of Contents for VRV X RXQ6-48ANR Series
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ6 48A N R Series SiME341909EA...
Page 289: ...SiME341909EA Wiring Diagrams Part 7 Appendix 283 RXQ10 12ARYFK 2D124184...
Page 290: ...Wiring Diagrams SiME341909EA 284 Part 7 Appendix RXQ14 16ARYFK 2D124183...
Page 295: ...SiME341909EA Wiring Diagrams Part 7 Appendix 289 FXMQ40 50 63 80 100ARV1 3D127112 04 59...