background image

•  Outdoor Units • VRV HEAT RECOVERY • REYHQ16-24P  

1

4

•  VRV Systems • Outdoor Units  

23

4

Capacity tables

4 - 4

Capacity correction factor

REYHQ16P

Rate of change in cooling capacity

Rate of change in heating capacity

3D058183A

NOTES

1

These figures illustrate the rate of change in capacity of a standard indoor unit system at maximum load (with the thermostat set to maximum) under 
standard conditions.
Moreover, under partial load conditions there is only a minor deviation from the rate of change in capacity shown in the above figures.

2

With this outdoor unit, evaporating pressure constant control when cooling, and condensing pressure constant control when heating is carried out.

3

Method of calculating A/C (cooling / heating) capacity:
The maximum A/C capacity of the system will be either the total A/C capacity of the indoor units obtained from capacity characteristic table or the 
maximum A/C capacity of outdoor units as mentioned below, whichever smaller.
Calculating A/C capacity of outdoor units

Condition: Indoor unit combination ratio does not exceed 100%
Maximum A./C capacity of outdoor units = A/C capacity of outdoor units obtained from performance characteristics table at the 100% combination

x capacity change rate due to piping length to the farthest indoor unit

Condition: Indoor unit combination ratio exceeds 100%
Maximum A./C capacity of outdoor units = A/C capacity of outdoor units obtained from capacity characteristics table at the combination

x capacity change rate due to piping length to the farthest indoor unit

4

When overall equivalent pipe length is 90m or more, the diameter of the main liquid pipes (outdoor unit-branch sections) must be increased.
When level difference is 50m or more, the diameter of the main gas and liquid pipes (outdoor unit-brach sections) must be increased.
[Diameter of above case]

*If available on the site, use this size. Otherwise, not increased.

5

When the main sections of the interunit liquid pipe diameters are increased the overall equivalent length should be calculated as follows. (Heating only)
Overall equivalent length = Equivalent length to main pipe x Correction  Equivalent length after branching
Choose a correction factor from the following table.
Example in case of REYQ18PY1

In the above case (Heating)
Overall equivalent length = 80m x 0.3 + 40m = 64m
The correction factor in capacity when Hp=0m is thus approximately 1.0

6

In combination wich does not include cooling onlyindoor unit.
Calculate the equivalent length pipe by the following when you calculate cooling capacity
Overall equivalent length = Equivalent length to main pipe x 0.5 + Equivalent length after branching
Example

In the above case (Cooling)
Overall equivalent length = 80m x 0.5 + 40m = 80m
The correction factor in capacity when Hp=0m is thus approximately 0.88

EXPLANATION OF SYMBOLS

H

p

: Level difference (m) between indoor and outdoor units where indoor unit in inferior position

H

M

: Level difference (m) between indoor and outdoor units where indoor unit in superior position

L

: Equivalent pipe length (m) 

α

: Rate of change in cooling / heating capacity

[Diameter of pipe (standard size)]

Model

Liquid

REYQ16P9Y1B

Ø15.9

Model

Liquid

REYQ16P9Y1B

Ø12.7

Equivalent lenght

Equivalent lenght

Indoor unit

Outdoor unit

Liquid pipe: 
Standard size

Branch BS-unit

Equivalent lenght

Equivalent lenght

Indoor unit

Outdoor unit

Branch

BS-unit

Summary of Contents for VRV Series

Page 1: ...ables 6 Combination table 6 Cooling capacity tables 7 Heating capacity tables 15 Capacity correction factor 23 5 Dimensional drawing centre of gravity 27 Dimensional drawing 27 Centre of gravity 28 6...

Page 2: ...2 088 Nr of Rows 54 54 54 54 Fin Pitch mm 2 2 2 2 Nr of Passes 18 18 18 21 18 21 21 21 Face Area m 2 112 2 112 2 112 2 481 2 112 2 481 2 481 2 481 Nr of Stages 2 2 2 2 Tube type Hi XSS 8 Fin Fin type...

Page 3: ...erature Capacity Control Method Inverter controlled Capacity Control 100 Safety devices HPS Fan motor driver overload protector Over current relay Inverter overload protector PC board fuse Standard Ac...

Page 4: ...rcuit breaker and the ground fault circuit interrupter earth leakage circuit breaker MSC means the maximum current during start up of the compressor Maximum allowable voltage range variation between p...

Page 5: ...al technical standard setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipment with rated 75A 2 European International technical stand...

Page 6: ...RQ23M64T o o o o o KHRQ23M75T o o Ountdoor unit multipiping connection kit for H R BHFQ23P907 o BHFQ23P1357 o Central drain pan kit KWC26C280 o o o See note 4 See note 4 KWC26C450 o o See note 4 See n...

Page 7: ...V Systems Outdoor Units 6 Outdoor Units VRV HEAT RECOVERY REYHQ16 24P 4 Capacity tables 4 1 Combination table REYHQ P 4TW31481 1 UNIT REMQ8P9 REMQ10P8 REMHQ12P8 REYHQ16P 2 REYHQ20P 1 1 REYHQ22P 1 1 RE...

Page 8: ...7 50 4 8 4 51 1 8 4 51 7 8 5 53 0 8 5 54 4 8 6 25 36 4 5 59 43 5 7 2 49 7 8 7 50 3 8 8 51 0 8 8 52 3 8 9 53 6 9 0 27 36 4 5 97 43 5 7 7 49 0 9 1 49 6 9 2 50 3 9 2 51 6 9 3 52 9 9 4 29 36 4 6 37 43 5 8...

Page 9: ...2 69 25 4 3 21 29 5 3 76 31 5 4 04 33 5 4 34 37 6 4 94 41 7 5 56 20 21 3 2 74 25 4 3 27 29 5 3 83 31 5 4 12 33 5 4 42 37 6 5 04 41 7 5 71 21 21 3 2 76 25 4 3 30 29 5 3 87 31 5 4 16 33 5 4 46 37 6 5 1...

Page 10: ...1 64 4 11 2 66 0 11 3 67 7 11 4 25 45 4 7 40 54 1 9 5 61 8 11 6 62 7 11 6 63 5 11 7 65 1 11 8 66 7 11 9 27 45 4 7 90 54 1 10 2 60 9 12 1 61 7 12 1 62 6 12 2 64 2 12 3 65 8 12 4 29 45 4 8 43 54 1 10 9...

Page 11: ...51 9 7 22 18 26 5 3 56 31 6 4 25 36 7 4 98 39 2 5 35 41 7 5 74 46 8 6 54 51 9 7 36 20 26 5 3 62 31 6 4 32 36 7 5 07 39 2 5 46 41 7 5 85 46 8 6 67 51 9 7 56 21 26 5 3 65 31 6 4 36 36 7 5 12 39 2 5 51 4...

Page 12: ...8 12 8 70 7 12 9 72 5 13 0 74 3 13 1 25 49 8 8 52 59 4 11 0 67 9 13 3 68 8 13 4 69 7 13 4 71 5 13 6 73 3 13 7 27 49 8 9 10 59 4 11 7 66 9 13 9 67 8 13 9 68 7 14 0 70 5 14 1 72 3 14 3 29 49 8 9 7 59 4...

Page 13: ...38 57 0 8 31 18 29 1 4 10 34 7 4 89 40 3 5 73 43 1 6 16 45 9 6 61 51 4 7 52 57 0 8 47 20 29 1 4 17 34 7 4 98 40 3 5 84 43 1 6 28 45 9 6 74 51 4 7 67 57 0 8 71 21 29 1 4 21 34 7 5 02 40 3 5 89 43 1 6 3...

Page 14: ...8 76 4 13 9 77 4 14 0 79 3 14 1 81 3 14 2 25 54 3 9 2 64 7 11 8 74 3 14 4 75 3 14 5 76 3 14 6 78 3 14 7 80 2 14 9 27 54 3 9 8 64 7 12 6 73 2 15 0 74 2 15 1 75 2 15 2 77 2 15 3 79 1 15 5 29 54 3 10 4...

Page 15: ...3 62 1 8 9 18 31 7 4 41 37 8 5 26 43 9 6 16 46 9 6 63 50 0 7 10 56 0 8 1 62 1 9 1 20 31 7 4 48 37 8 5 35 43 9 6 27 46 9 6 75 50 0 7 24 56 0 8 2 62 1 9 4 21 31 7 4 52 37 8 5 40 43 9 6 33 46 9 6 82 50 0...

Page 16: ...6 3 10 8 36 3 11 0 36 2 11 2 36 1 11 6 9 5 10 0 37 4 10 21 37 3 10 6 37 2 11 0 37 1 11 2 37 1 11 4 37 0 11 8 8 5 9 1 38 2 10 4 38 1 10 7 38 0 11 1 37 9 11 3 37 9 11 5 37 8 11 9 7 0 7 6 39 6 10 6 39 5...

Page 17: ...8 11 0 35 9 12 6 35 9 12 9 35 0 12 7 33 9 12 2 32 8 11 7 30 5 10 7 9 5 10 0 36 8 12 7 36 7 13 0 35 0 12 3 33 9 11 8 32 8 11 4 30 5 10 4 8 5 9 1 37 6 12 8 37 3 12 9 35 0 12 0 33 9 11 5 32 8 11 1 30 5...

Page 18: ...12 9 44 4 13 4 9 5 10 0 45 9 11 7 45 8 12 2 45 7 12 6 45 6 12 9 45 6 13 1 45 4 13 6 8 5 9 1 46 9 11 9 46 8 12 4 46 7 12 8 46 6 13 0 46 5 13 3 46 4 13 7 7 0 7 6 48 6 12 2 48 4 12 6 48 3 13 1 48 3 13 3...

Page 19: ...11 0 44 1 14 6 44 0 14 9 43 8 15 1 42 3 14 5 40 9 13 9 38 1 12 8 9 5 10 0 45 2 14 7 45 1 15 0 43 8 14 7 42 3 14 1 40 9 13 5 38 1 12 5 8 5 9 1 46 1 14 8 46 0 15 1 43 8 14 3 42 3 13 7 40 9 13 2 38 1 12...

Page 20: ...4 9 48 4 15 2 48 3 15 7 9 5 10 0 49 9 13 7 49 8 14 2 49 7 14 8 49 6 15 1 49 5 15 4 49 4 15 9 8 5 9 1 51 0 13 9 50 9 14 4 50 8 15 0 50 7 15 3 50 6 15 5 50 5 16 1 7 0 7 6 52 9 14 3 52 8 14 8 52 6 15 3 5...

Page 21: ...8 11 0 48 0 17 1 47 9 17 5 47 8 17 8 46 7 17 4 45 2 16 7 42 1 15 4 9 5 10 0 49 1 17 3 49 0 17 6 48 3 17 6 46 7 16 9 45 2 16 3 42 1 14 9 8 5 9 1 50 2 17 4 50 1 17 7 48 3 17 1 46 7 16 5 45 2 15 8 42 1 1...

Page 22: ...17 1 56 5 17 3 56 3 17 9 9 5 10 0 58 2 15 8 58 1 16 4 58 0 17 0 57 9 17 3 57 8 17 6 57 7 18 1 8 5 9 1 59 5 16 1 59 3 16 6 59 2 17 2 59 1 17 5 59 0 17 7 58 9 18 3 7 0 7 6 61 6 16 4 61 4 17 0 61 3 17 5...

Page 23: ...17 8 45 8 16 4 9 8 11 0 56 0 19 3 55 9 19 7 52 5 18 2 50 8 17 5 49 1 16 8 45 8 15 5 9 5 10 0 57 3 19 5 55 9 19 1 52 5 17 7 50 8 17 0 49 1 16 4 45 8 15 1 8 5 9 1 58 5 19 6 55 9 18 6 52 5 17 3 50 8 16 6...

Page 24: ...is 90m or more the diameter of the main liquid pipes outdoor unit branch sections must be increased When level difference is 50m or more the diameter of the main gas and liquid pipes outdoor unit bra...

Page 25: ...3 1 4 VRV Systems Outdoor Units 24 Outdoor Units VRV HEAT RECOVERY REYHQ16 24P 4 Capacity tables 4 4 Capacity correction factor J J...

Page 26: ...uid pipes outdoor unit branch sections must be increased When level difference is 50m or more the diameter of the main gas and liquid pipes outdoor unit brach sections must be increased Diameter of ab...

Page 27: ...3 1 4 VRV Systems Outdoor Units 26 Outdoor Units VRV HEAT RECOVERY REYHQ16 24P 4 Capacity tables 4 4 Capacity correction factor H H B J H B J...

Page 28: ...22 5 mm Oblong holes foundation bolt hole No Parts name Remarks 4 Pressure equalizer pipe connection port 19 1 Brazing connection See note 2 5 Grounding terminal inside of switch box M8 6 Power cord r...

Page 29: ...ERY REYHQ16 24P 5 Dimensional drawing centre of gravity 5 2 Centre of gravity REMHQ12P8 3D057578B Center of foundation bolt hole Center of foundation bolt hole Center of foundation bolt hole Center of...

Page 30: ...Outdoor Units VRV HEAT RECOVERY REYHQ16 24P 1 6 VRV Systems Outdoor Units 29 6 Piping diagram H 2P8 J...

Page 31: ...valve pipe F5U Field fusef R90 Resistor current sensor Y3S 4 way valve H E Gas F400U Fuse T 63A 250V A2P R95 Resistor current limiting Y4S RMTL Y5S Hots gas H1P H8P Pilotlamp service monitor orange H...

Page 32: ...erates 2 Sound pressure level is a relative value depending on the distance and acoustic environment For more details please refer to sound level drawings 3 Mentioned values are theoretical values bas...

Page 33: ...3 1 8 VRV Systems Outdoor Units 32 Outdoor Units VRV HEAT RECOVERY REYHQ16 24P 8 Sound data 8 2 Sound power spectrum H 2P8...

Page 34: ...than are catered for in the above patterns your layout should take account of the possibility of short circuits 4 The units should be installed to leave insufficient space at the front for the on sit...

Page 35: ...is built shall have rough finish 4 A drain ditch shall be made around the foundation to thoroughly drain water from the equipment installation area 5 When installing the equipment on a roof the floor...

Page 36: ...pipe length Pipe length from first refrigerant branch kit either refnet joint or refnet header to indoor unit 40 m See note 2 Example unit 8 b c d e s 40 m Example unit 6 b l 40 m unit 8 m n p 40 m Ex...

Page 37: ...1 0 kg X 1 x 22 2 x0 37 X 2 x 19 1 x0 26 X 3 x 15 9 x0 18 X 4 x 12 7 x0 12 X 5 x 9 5 x0 059 X 6 x 6 4 x0 022 A B x 1 02 REY H Q A 1 0 kg 1 5 kg 2 0 kg 2 5 kg 3 0 kg 3 5 kg 4 0 kg 4 5 kg REYHQ 16 Hp 2...

Page 38: ...on Operation range NOTES 1 These figures assume the following operation conditions Indoor and outdoor units Equivalent pipe length 7 5m Level difference 0m 2 Depending on operation and installation co...

Reviews: