background image

Outdoor Air Processing Unit

FXMQ-MFVJU

EDUS39-900B-F10

202103

Engineering Data

60 Hz

Summary of Contents for VRV Series

Page 1: ...Outdoor Air Processing Unit FXMQ MFVJU EDUS39 900B F10 202103 Engineering Data 60 Hz...

Page 2: ......

Page 3: ...nsions 5 4 Center of Gravity 7 5 Piping Diagrams 8 6 Wiring Diagrams 9 7 Electric Characteristics 11 8 Capacity Tables 12 9 Operation Limit 15 10 Fan Performances 18 11 Sound Levels Reference Data 21...

Page 4: ...utdoor air processing unit can be connected to the same refrigerant line enabling enhanced design flexibility Design flexibility with a capacity range up to 96 MBH The nominal airflow rates are 635 98...

Page 5: ...for fan motor Fuse Thermal protector for fan motor Refrigerant control Electronic expansion valve Electronic expansion valve H5 Connectable outdoor units R410A VRV series R410A VRV series Standard ac...

Page 6: ...le outdoor units R410A VRV series Standard accessories Operation manual Installation manual Sealing pads Screws Clamps Connection pipes Note 1 Nominal cooling capacities are based on the following con...

Page 7: ...5 FXMQ MFVJU EDUS39 900B F10 3 Dimensions FXMQ48MFVJU 3D065452A Unit in...

Page 8: ...6 FXMQ MFVJU EDUS39 900B F10 FXMQ72 96MFVJU 3D065453A Unit in...

Page 9: ...of Gravity FXMQ48 96MFVJU Unit in 4D065444 Model FXMQ48MFVJU FXMQ72MFVJU FXMQ96MFVJU Product Mass 190Lbs 271Lbs 271Lbs AA 30 11 16 54 5 16 54 9 16 AB 27 3 8 51 51 AC 23 5 8 22 7 16 22 7 16 AD 9 13 16...

Page 10: ...8 FXMQ MFVJU EDUS39 900B F10 5 Piping Diagrams FXMQ48 96MFVJU Unit in Model Gas Liquid FXMQ48MFVJU 5 8 3 8 FXMQ72MFVJU 3 4 FXMQ96MFVJU 7 8 4D018650D...

Page 11: ...CORDANCE WITH THE ATTACHED INSTRUCTION MANUAL 3 IN CASE CONNECTING THE INPUT WIRES FROM OUTSIDE FORCED OFF OR ON OFF CONTROL OPERATION CAN BE SELECTED BY REMOTE CONTROLLER IN DETAILS REFER TO THE INST...

Page 12: ...ETIC RELAY M1P KSR MAGNETIC RELAY Y1S M1F MOTOR FAN Q1M THERMAL PROTECTOR M1F EMBEDDED 135 C R1T THERMISTOR SUCTION AIR R2T THERMISTOR COIL LIQUID R3T THERMISTOR COIL GAS R4T THERMISTOR DISCHARGE AIR...

Page 13: ...0 380 3 3 638 638 Symbol MCA Min Circuit Amps A MOP Max Overcurrent Protective Device A KW Fan Motor Rated Output kW FLA Full Load Amps A IFM Indoor Fan Motor SCCR Short Circuit Current Rating Note 1...

Page 14: ...r air temperature FWB FDB 19 23 27 31 35 39 43 51 55 Capacity MBh MBh MBh MBh MBh MBh MBh MBh MBh 22 32600 32600 32 30000 37 26600 26600 26600 42 21500 21500 21500 52 16800 16800 16800 57 12100 12100...

Page 15: ...perature FWB FDB 19 23 27 31 35 39 43 51 55 Capacity MBh MBh MBh MBh MBh MBh MBh MBh MBh 22 50700 50700 32 47000 37 41200 41200 41200 42 33800 33800 33800 52 26300 26300 26300 57 18900 18900 18900 Not...

Page 16: ...emperature FWB FDB 19 23 27 31 35 39 43 51 55 Capacity MBh MBh MBh MBh MBh MBh MBh MBh MBh 22 63700 63700 32 59000 37 51800 51800 51800 42 42300 42300 42300 52 33200 33200 33200 57 23700 23700 23700 N...

Page 17: ...ay not match the temperature setting for too large outdoor air processing capacity Thermostat OFF may be carried out NOTE 1 These figures assume the following operating conditions Indoor and outdoor u...

Page 18: ...the temperature setting for too large outdoor air processing capacity Thermostat OFF may be carried out NOTE 1 These figures assume the following operating conditions Indoor and outdoor units Equivale...

Page 19: ...the temperature setting for too large outdoor air processing capacity Thermostat OFF may be carried out NOTE 1 These figures assume the following operating conditions Indoor and outdoor units Equival...

Page 20: ...18 FXMQ MFVJU EDUS39 900B F10 10 Fan Performances FXMQ48MFVJU 3D065649B...

Page 21: ...19 FXMQ MFVJU EDUS39 900B F10 FXMQ72MFVJU 3D065650B...

Page 22: ...20 FXMQ MFVJU EDUS39 900B F10 FXMQ96MFVJU 3D065651B...

Page 23: ...erence Data 11 1 Overall n Location of microphone 6 6 ft 4 9 ft DUCT DISCHARGE SUCTION MICROPHONE DUCT 3 3 ft Note 1 Operation noise differs with operation and ambient conditions dBA Model 208 230 V 6...

Page 24: ...22 FXMQ MFVJU EDUS39 900B F10 11 2 Octave Band Level 208 230 V 60 Hz FXMQ48MFVJU FXMQ72MFVJU C 4D068575 C 4D068576 FXMQ96MFVJU C 4D068577...

Page 25: ...0 KDJ3705L280 Long life replacement filter KAF371M140 KAF371M280 C 3D065445 Note H1 Filter chamber has a suction type flange Main unit does not have Dimensions and weight of the equipment may vary dep...

Page 26: ......

Page 27: ......

Page 28: ...or explosion Use only those parts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessori...

Reviews: