SiAF332111E
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
105
1.4.21 External Static Pressure Settings
Make external static pressure setting automatically using automatic airflow adjustment
(11 (21)-7), or manually using external static pressure settings (13 (23)-6).
FXMQ-PB
: Factory setting
1 FXMQ40PB cannot be set to 180 or 200 Pa.
2 FXMQ50-125PB cannot be set to 30 Pa.
3 FXMQ140PB cannot be set to 30 Pa and 150-200 Pa.
1.4.22 Setting of Swing Patterns when Cooling Thermostat is OFF
In cooling operation, when the airflow direction is set to swing, flaps swing even when the
thermostat is OFF. This setting allows to change the airflow direction when the thermostat is
OFF.
: Factory setting
1.4.23 Setting of Circulation Airflow
This is to set whether the circulation airflow function is enabled or disabled.
: Factory setting
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
6
01
30 Pa (
2) (
3)
02
50 Pa
03
60 Pa
04
70 Pa
05
80 Pa
06
90 Pa
07
100 Pa
08
110 Pa
09
120 Pa
10
130 Pa
11
140 Pa
12
150 Pa (
3)
13
160 Pa (
3)
14
180 Pa (
1) (
3)
15
200 Pa (
1) (
3)
Mode
No.
First
Code No.
Second
Code No.
Fixed
Swing
13 (23)
7
01
Set Position
Swing
02
Set Position
P0
03
P0
P0
04
Set Position
Swing
05
Set Position
P2
06
P2
P2
07
Set Position
Swing
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
13
01
Disabled
02
Enabled
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...