SiE 00-07
Outline of Control (Outdoor Unit)
Function R-407C PLUS Series
61
3.13
Discharge Pipe Temperature Control
Controls the liquid injection and operating frequency to prevent abnormal increase of discharge pipe
temperature and compressor internal temperature.
3.13.1 Liquid Injection Control
Inverter compressor
Opens SVTi (Y3S) (solenoid valve for inverter compressor liquid injection) for 3 minutes after
software startup.
[Cooling]
DSHi: Inverter compressor discharge pipe superheated degree
= Tdi (Th3-1) - (HP equivalent saturation temperature)
Tdi: Inverter compressor discharge pipe temperature (Th3-1)
[Heating]
[Preparing Oil return and defrosting operation (1 min before operation start)]
[Oil return operation/defrosting operation]
SVTi (Y3S) is OFF at any case when inverter compressor stops.
STD compressor
[In cooling operation]
DSHs: STD compressor discharge pipe superheated degree
= Tds1, 2 (Th3-2) - (HP equivalent saturation temperature)
Tds1, 2 : STD compressor discharge pipe temperature (Th3-2)
Normal operation
SVTi : ON
DSHi
≥
40˚C
DSHi<15˚C
(V0826)
OR
&
DSHi<25˚C
10min elapsed
Normal operation
SVTi : ON
•
Tdi
≥
100˚C
•
LP<0.05MPa
•
(HP+0.10) / (LP+0.10)>8
•
Tdi<90˚C
•
LP>0.07MPa
•
2 min elapsed
(V0827)
OR
&
Preparing oil return
and defrosting
SVTi : ON
DSHi
≥
15˚C
Start oil return
& Defrost operation
(V0828)
Normal operation
SVTs1 (Y4S), SVTs2 (Y6S) : ON
10 min
DSHs1, DSHs2
≥
40˚C
DSHs1, DSHs2<15˚C
(V0829)
Summary of Contents for VRV R-407C PLUS Series
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07...
Page 11: ...Introduction SiE 00 07 x...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121...