Troubleshooting
Service manual
59
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform
a
check
of
the
compressor
body
thermistors.
See
348].
Possible cause:
Faulty compressor body thermistor or connector fault.
2
Perform a check of the main PCB. See
290].
Possible cause:
Faulty main PCB.
3
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant shortage.
4
Perform a check of the compressor. See
221].
Possible cause:
Faulty compressor.
5
Perform a check of the lower heat exchanger expansion valve. See
244].
Possible cause:
Faulty lower heat exchanger expansion valve.
6
Perform a check of the upper heat exchanger expansion valve. See
244].
Possible cause:
Faulty upper heat exchanger expansion valve.
7
Perform a check of the expansion valve(s) of the indoor unit(s). See service
manual of the respective indoor unit(s) for more information.
Possible cause:
Faulty indoor unit expansion valve.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.37 F4-01 – Wet operation caution
Trigger
Effect
Reset
Discharge superheat
<10˚C (SH
Discharge
=T
Discharge
−
T
condensation
).
Unit keeps running.
Automatic reset when
discharge superheat
>10˚C.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Check if the refrigerant circuit is correctly charged. See
Possible cause:
Refrigerant overcharge.
2
Check for the presence of non‑condensables and/or humidity in the
refrigerant circuit. See
363].
Possible cause:
Non‑condensables and/or humidity in the refrigerant circuit.
Summary of Contents for VRV IV+
Page 473: ......
Page 474: ......
Page 475: ......