8
|
Operation
Installer and user reference guide
26
R R8T7V1B
VRV IV heat pump for indoor installation
4P499898-1A – 2020.10
8 Operation
In this chapter
8.1 Operation range
Use the system in the following temperature and humidity ranges for safe and
effective operation.
Specification
5 HP
8 HP
Maximum capacity
Heating
16.0 kW
25.0 kW
Cooling
14.0 kW
22.4 kW
Outside ambient design
temperature
Heating
–20~15.5°C WB
Cooling
–5~46°C DB
Ambient design temperature of compressor unit
and heat exchanger unit
5~35°C DB
Maximum relative
humidity around the
compressor unit and heat
exchanger unit
Heating
50%
(a)
Cooling
80%
(a)
Special operation ranges are valid in case of using AHU. They can be found in the
installation/operation manual of the dedicated unit. Latest information can be
found in the technical engineering data.
8.2 Operating the system
8.2.1 About operating the system
▪
Operation procedure varies according to the combination of compressor unit,
heat exchanger unit, and user interface.
▪
To protect the unit, turn on the main power switch 6 hours before operation.
▪
If the main power supply is turned off during operation, operation will restart
automatically after the power turns back on again.