Operation manual

7

HXHD125A8V1B

VRV IV system indoor unit

4P404572-1 – 2015.04

Leaving water temperature control

In this mode, heating will be activated as required by the water
temperature set point. The set point can be set manually or through
the schedule timer or weather dependent (automatic).

Selecting space heating operation

1

Use the 

 button to switch ON/OFF space heating ( ).

Icon 

 appears on the display as well as the corresponding

water temperature set point.
The operation LED   lights up.

2

Use the 

 and 

 buttons to set the desired leaving

water temperature.

Temperature range for heating: 25°C~80°C (leaving water
temperature)
In order to avoid overheating, space heating is not operable
when the outdoor ambient temperature rises above a certain
temperature (see operation range).

Refer to "Remote controller schedule timer" for setup of the schedule
timer function.

Selecting weather dependent set point operation

When weather dependent operation is active, the leaving water
temperature is determined automatically depending on the outdoor
temperature: colder outdoor temperatures will result in warmer water
and vice versa. The unit has a floating set point. Activating this
operation will result in a lower power consumption than use with a
manually fixed leaving water set point.

During weather dependent operation, the user has the possibility to
shift up or down the target water temperature by a maximum of 5°C.
This shift value is the temperature difference between the
temperature set point calculated by the controller and the real set
point. E.g. a positive shift value means that the real temperature set
point will be higher than the calculated set point.

It is advised to use the weather dependent set point because it
adjusts the water temperature to the actual needs for space heating.
It will prevent the unit from switching too much between thermo ON
operation and thermo OFF operation when using the remote
controller room thermostat or external room thermostat.

1

Press the 

 button 1 time to select weather dependent set

point operation (or 2 times when the remote controller room
thermostat function is used).

Icon 

 appears on the display as well as the shift value. The

shift value is not shown in case it is 0.

2

Use the 

 and 

 buttons to set the shift value.

Range for the shift value: –5°C to +5°C

Icon 

 will be displayed as long as the weather dependent set

point operation is enabled.

3

Press the 

 button to deactivate weather dependent set point

operation.

The 

 and 

 buttons are used to set the leaving

water temperature.

Field settings define the parameters for the weather dependent
operation of the unit. Refer to 

"5.12. Field settings" on page 18

 for a

detailed description how to set one or more field settings.

[3-00] Low ambient temperature (Lo_A): low outdoor
temperature.

[3-01] High ambient temperature (Hi_A): high outdoor
temperature.

[3-02] Set point at low ambient temperature (Lo_Ti): the target
outgoing water temperature when the outdoor temperature
equals or drops below the low ambient temperature (Lo_A).

Note that the Lo_Ti value should be higher than Hi_Ti, as for
colder outdoor temperatures (i.e. Lo_A) warmer water is required.

[3-03] Set point at high ambient temperature (Hi_Ti): the target
outgoing water temperature when the outdoor temperature
equals or rises above the high ambient temperature (Hi_A).

Note that the Hi_Ti value should be lower than Lo_Ti, as for
warmer outdoor temperatures (i.e. Hi_A) less warm water
suffices.

NOTICE

When an external room thermostat is installed, the
thermo ON/OFF is determined by the external room
thermostat. The remote controller is then operated in
the leaving control mode and is not functioning as a
room thermostat.

The remote controller ON/OFF status always has
priority over the external room thermostat!

INFORMATION

During this operation, instead of showing the water
temperature set point, the controller shows the shift value
which can be set by the user.

T

t

Target water temperature

T

A

Ambient (outdoor) temperature

Shift value

= Shift value

INFORMATION

If by mistake the value of [3-03] is set higher than the value
of [3-02], the value of [3-03] will always be used.

Lo_Ti

Lo_A

Hi_A

T

A

T

t

+ 05

00

– 05

Hi_Ti

Shift value

Summary of Contents for VRV IV HXHD125A8V1B

Page 1: ...OPERATION MANUAL HXHD125A8V1B system indoor unit...

Page 2: ...by a person responsible for their safety Children shall be supervised to ensure that they do not play with the appliance 1 DEFINITIONS 1 1 Meaning of warnings and symbols Warnings in this manual are...

Page 3: ...Scope of this manual This manual describes how to start up and switch off the unit set parameters and configure the schedule timer by means of the controller maintain the unit and solve operational p...

Page 4: ...l light up and the unit will start For further details and advised settings see 5 3 Space heating operation on page 6 Domestic water heating only if domestic hot water tank option is installed Automat...

Page 5: ...the current temperature of the installation either leaving water set point temperature or actual room temperature When changing the room temperature set point the set point will be flashing for 5 seco...

Page 6: ...the indoor unit outdoor ambient temperature actual room temperature and domestic hot water temperature and in schedule timer programming mode 29 LEAVING WATER TEMPERATURE ADJUST BUTTONS and These but...

Page 7: ...back function can for instance be activated during the night because the temperature demands during night and day are not the same The setback function is configured through field settings Refer to th...

Page 8: ...Press the button 1 time to select weather dependent set point operation or 2 times when the remote controller room thermostat function is used Icon appears on the display as well as the shift value Th...

Page 9: ...ight when space heating requirements are lower until the storage temperature set point is reached The heated water is stored in the domestic hot water tank at a higher temperature so it can fulfil the...

Page 10: ...igher too so that storage temperature set point can be set lower in order to keep the overall equivalent hot water amount the same during the whole year Therefor it is recommended to use this function...

Page 11: ...tting 4 00 is set to ON 5 5 Other operation modes Start up operation During start up the icon displays indicating that the heat pump is starting up and is not working in a steady state condition Defro...

Page 12: ...n is controlled by the schedule timer The actions programmed in the schedule timer will be executed automatically The schedule timer is enabled icon displayed or disabled icon not displayed by pressin...

Page 13: ...nd will remain active until the next programmed command 19 00 occurs So in order to know the actual setting one should consult the last programmed command It is clear that the last programmed command...

Page 14: ...out the form at the very end of this manual This form can help you define the required actions for each day Take your time to enter all data accurately Try to program the actions in a chronological w...

Page 15: ...and buttons to set the room temperature 11 Use the button to select to switch heating and the remote controller off to select automatic temperature calculation for leaving water temperature Use the a...

Page 16: ...button to select the action number you would like to program or to modify 8 Use the and buttons to set the correct action time 9 Use the button to select or deselect as action 10 Repeat steps 7 to 9...

Page 17: ...odify 7 Use the and buttons to set the correct action time 8 Use the button to select or deselect as action 9 Repeat steps 6 to 8 to program the other actions of the selected mode When all actions hav...

Page 18: ...o step 2 by pressing the button Deleting one or more programmed actions Deleting one or more programmed actions is done at the same time as storing the programmed actions When all actions for one day...

Page 19: ...The current selected field setting code is indicated 2 with the set value displayed to the right 1 2 Press the button to select the appropriate field setting first code 3 Press the button to select th...

Page 20: ...mperature Lo_Ti 70 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 45 25 80 1 C 4 Disinfection function 00 Status disinfection operation 1 ON 0 1 01 Disinfection operation day selection Fri M...

Page 21: ...icable Do not change the default value 20 03 Not applicable Do not change the default value 5 04 Not applicable Do not change the default value 0 d Domestic water heating retention times 00 Installati...

Page 22: ...rmation for diagnosing and correcting certain problems which may occur with the unit WARNING If the supply cord is damaged it must be replaced by the manufacturer its agent or similar qualified person...

Page 23: ......

Page 24: ...4P404572 1 2015 04 Copyright 2015 Daikin...

Reviews: