[Refrigerant Charging Operation Procedure]
STEP 1
Open the liquid pipe, suction gas pipe, HP/LP gas pipe and equalizer pipe shutoff
valves (The valve A~C must be closed. The valve A~C means the valves in the figure
of REYQ8~16PY1 on page 159.)
STEP 2
• Close the EL. COMPO. BOX lid and all front panel except on the side of the EL.
COMPO. BOX (*1) and turn the power to the outdoor unit and all connected indoor
units. (*2)
• After H2P stop blinking (about 12 minutes after turning on the power), check LED
displays as shown in Table : Display of normal system and the system is normal
state.
If H2P is blinking, check the malfunction code in the remote controller, and correct
the malfunction in accordance with [Remote controller display malfunction code] in
chapter 1.2.5.2.2.
(*1) Lead the refrigerant charge hose etc from the pipe intake. All front panels must be closed
at the procedure (3).
(*2) • If you perform the refrigerant charging operation within the refrigerant system that have
the power off unit, the operation cannot finish properly.
For confirming the number of the outdoor and indoor units with the power on, see [How
to check how many units are connected] in chapter 1.2.5.1. In case of a multi system,
turn on the power to all outdoor units in the refrigerant system.
• To energize the crankcase heater, make sure to turn on for 6 hours before starting
operation.
Table : Display of normal system
LED display:
h
...OFF,
k
...ON,
l
...Blinking
(*) How to distinguish the master unit, slave unit 1, and slave unit 2 in the multi system.
STEP 3
Charge the remained refrigerant by additional refrigerant charging operation of
service mode.
About the method of additional refrigerant charging operation, refer to the [Service
Precaution] labe (lower) attached on the EL. COMPO. BOX lid of the outdoor unit.
STEP 4
Close the valve A if the “additional charging amount” of refrigerant was charged, and
push the RETURN button (BS3) once.
LED display
(Default status of shipped)
SERV.
MONITOR
MODE
TEST/
HWL
C/H SELECTOR
L.N.O.P DEMA-ND MULTI
IND
MASTER SLAVE
HAP
H1P
H2P
H3P
H4P
H5P
H6P
H7P
H8P
Single system
l
h
h
k
h
h
h
h
h
Multi
system
(*)
Master unit
l
h
h
k
h
h
h
h
k
Slave unit 1
l
h
h
h
h
h
h
h
l
Slave unit 2
l
h
h
h
h
h
h
h
h
Method 1 : By the H8P (MULTI) LED display
k
(ON) : Master unit
l
(Blinking) : Slave unit 1
7
(OFF) : Slave unit 2
Method 2 : By the transmission wiring to indoor unit
Transmission wiring is connected : Master unit
Transmission wiring is not connected : Slave unit 1 or Slave unit 2
EL. COMPO.BOX lid
Inspection door
[Service Precaution] label (upper)
[Service Precaution] label (lower)
Summary of Contents for VRV III REYQ8PY1
Page 1: ...REYQ8 48PY1 R 410A Heat Recovery 50Hz Si37 701...
Page 59: ...Specifications Si37 701 48 Specifications...
Page 105: ...Refrigerant Flow for Each Operation Mode Si37 701 94 Refrigerant Circuit...
Page 230: ...Si37 701 Troubleshooting by Remote Controller Troubleshooting 219...
Page 374: ...Si37 701 Piping Diagrams Appendix 363 REYQ14P 16PY1 3D058153A S2NPL S1NPH...
Page 375: ...Piping Diagrams Si37 701 364 Appendix REMQ8PY1 3D057743...
Page 376: ...Si37 701 Piping Diagrams Appendix 365 REMQ10PY1 12PY1 3D057742...
Page 377: ...Piping Diagrams Si37 701 366 Appendix REMQ14PY1 16PY1 3D057741...
Page 382: ...Si37 701 Piping Diagrams Appendix 371 1 3 BS Unit 4D057985A...
Page 384: ...Si37 701 Wiring Diagrams for Reference Appendix 373 REYQ14 16PY1 3D056774C...
Page 385: ...Wiring Diagrams for Reference Si37 701 374 Appendix REMQ8PY1 3D055307E...
Page 386: ...Si37 701 Wiring Diagrams for Reference Appendix 375 REMQ10 12PY1 3D055308E...
Page 387: ...Wiring Diagrams for Reference Si37 701 376 Appendix REMQ14P 16PY1 3D055309E...
Page 392: ...Si37 701 Wiring Diagrams for Reference Appendix 381 FXCQ40M 50M 80M 125MVE 3D039557A...
Page 394: ...Si37 701 Wiring Diagrams for Reference Appendix 383 FXZQ20M 25M 32M 40M 50M8V1B 3D038359...
Page 395: ...Wiring Diagrams for Reference Si37 701 384 Appendix FXKQ25MA 32MA 40MA 63MAVE 3D039564C...
Page 399: ...Wiring Diagrams for Reference Si37 701 388 Appendix FXDYQ180M 200M 250MV1...
Page 402: ...Si37 701 Wiring Diagrams for Reference Appendix 391 FXMQ200MA 250MAVE 3D039621B...
Page 403: ...Wiring Diagrams for Reference Si37 701 392 Appendix FXHQ32MA 63MA 100MAVE 3D039801D...
Page 406: ...Si37 701 Wiring Diagrams for Reference Appendix 395 2 4 BS Unit 3D055928C...
Page 423: ...Piping Installation Point Si37 701 412 Appendix...
Page 427: ...Example of Connection R 410A Type Si37 701 416 Appendix...
Page 433: ...Method of Checking the Inverter s Power Transistors and Diode Modules Si37 701 422 Appendix...
Page 447: ...Si37 701 iv Index...
Page 451: ...Si37 701 viii Drawings Flow Charts...