Troubleshooting by Remote Controller
SiBE37-701
246
Troubleshooting
k
: ON
h
: OFF
l
: Blink
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
Referred
Indoor Unit
A0
l
l
l
Error of external protection device
A1
l
l
l
PC board defect
A3
l
l
l
Malfunction of drain level control system (S1L)
A6
l
l
l
Fan motor (M1F) lock, overload
Malfunction of indoor unit fan motor
Overload/Overcurrent/Lock of indoor unit fan motor
A7
k
h
l
Malfunction of swing flap motor (M1S)
A9
l
l
l
Electronic expansion valve malfunction
Malfunction of electronic expansion valve coil
AF
k
h
l
Drain level above limit
AH
k
h
l
Malfunction of air filter maintenance
—
AJ
l
l
l
Malfunction of capacity determination device
C4
l
l
l
Malfunction of thermistor (R2T) for heat exchanger
C5
l
l
l
Malfunction of thermistor (R3T) for gas pipes
C9
l
l
l
Malfunction of thermistor (R1T) for suction air
CJ
k
k
k
Malfunction of thermostat sensor in remote
controller
Outdoor Unit
E1
l
l
l
PC board defect
E3
l
l
l
Actuation of high pressure switch
E4
l
l
l
Actuation of low pressure sensor
E5
l
l
l
Inverter compressor motor lock
E6
l
l
l
STD copmressor motor overcurent/lock
E7
l
l
l
Malfunction of outdoor unit fan motor
E9
l
l
l
Malfunction of moving part of electronic expansion
valve (Y1E ~ Y5E)
F3
l
l
l
Abnormal discharge pipe temperature
F6
l
l
l
Refrigerant overcharged
F9
l
l
l
Malfunction of BS unit electronic expansion valve
H7
l
l
l
Abnormal outdoor fan motor signal
H9
l
l
l
Malfunction of thermistor (R1T) for outdoor air
J2
l
l
l
Current sensor malfunction
J3
l
l
l
Malfunction of discharge pipe thermistor (R31T,
R32T, R33T)
J4
l
l
l
Malfunction of temperature sensor for heat
exchanger gas (R2T or R11T)
J5
l
l
l
Malfunction of thermistor (R8T or R10T) for suction
pipe
J6
l
l
l
Malfunction of thermistor (R4T or R12T) for outdoor
unit heat exchanger
J7
l
l
l
Malfunction of liquid pipe thermistor 1 (R6T, R9T or
R14T)
J8
l
l
l
Malfunction of liquid pipe thermistor 2 (R7T or
R15T)
J9
l
l
l
Malfunction of subcooling heat exchanger gas pipe
thermistor (R5T or R13T)
JA
l
l
l
Malfunction of high pressure sensor
JC
l
l
l
Malfunction of low pressure sensor
L1
l
l
l
Malfunction of inverter PC board
L4
l
l
l
Malfunction of inverter radiating fin temperature rise
L5
l
l
l
Momentary overcurrent of inverter compressor
L8
l
l
l
Momentary overcurrent of inverter compressor
L9
l
l
l
Inverter compressor starting failure
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...