SiBE37-701
Troubleshooting by Indication on the Remote Controller
Troubleshooting
287
3.21
“
F6
”
Outdoor Unit: Refrigerant Overcharged
Remote
Controller
Display
F6
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Excessive charging of refrigerant is detected by using the outside air temperature, heat
exchanging deicer temperature and liquid pipe temperature during a check run.
Malfunction
Decision
Conditions
When the amount of refrigerant, which is calculated by using the outside air temperature, heat
exchanging deicer temperature and liquid pipe temperature during a check run, exceeds the
standard.
Supposed
Causes
Refrigerant overcharge
Misalignment of the outside air thermistor
Misalignment of the heat exchanging deicer thermistor
Misalignment of the liquid pipe thermistor
Troubleshooting
∗
Refer to “Thermistor Resistance / Temperature Characteristics” table on P437.
(V2797)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Are the
above thermistor
installed on pipes
correctly?
Check the mounting condition of
the temperature sensors of the
outside air thermistor, heat
exchanging deicer thermistor and
liquid pipe thermistor in the piping.
Remove the outside air thermistor,
heat exchanging deicer thermister
and the liquid pipe thermistor from
the outdoor PC board and measure
resistance with a tester.
Is the
characteristic of the
above thermistor
normal?
Refrigerant overcharged.
YES
NO
NO
Replace thermistor.
Install thermistor correctly.
YES
Summary of Contents for VRV III REYQ10PY1B
Page 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Page 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Page 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Page 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Page 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Page 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Page 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Page 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Page 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Page 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Page 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Page 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Page 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Page 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Page 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Page 447: ...Example of connection SiBE37 701 436 Appendix ...
Page 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Page 467: ...SiBE37 701 iv Index ...